3.7 Display of the alarms and the respective latching bits of digital sensors
Display of the local alarms generated by the DGC-06 as well as of the respective latching bits of
digital sensors – sensor addresses 1 to 96, Modbus register addresses 1201 to 1296
3.8 Display of the alarms and the respective latching bits of analog sensors
Display of the local alarms generated by the DGC-06 as well as of the respective latching bits of
analog sensors – sensor addresses 1 to 32, Modbus register addresses 2201 to 2232
Figure 6: Display of the alarms and the respective latching bits of analog sensors
Here, the representation in the hexadecimal form is easier to read because the data are transmitted
in the following form:
0xFFFF =
There are 4 status bits for the 4 alarm stages each.
1 = alarm or latching active
0 = alarm or latching not active
The above example:
There are 2 local alarms at DP1, with the 2. being in latching mode.
The 1. alarm generated by the DGC-06 is present at DP4.
The 1. alarm generated by the DGC-06 is present at AP5.