3.7 Display of the alarms and the respective latching bits of digital sensors
Display of the local alarms generated by the DGC-06 as well as of the respective latching bits of
digital sensors sensor addresses 1 to 96, Modbus register addresses 1201 to 1296
3.8 Display of the alarms and the respective latching bits of analog sensors
Display of the local alarms generated by the DGC-06 as well as of the respective latching bits of
analog sensors sensor addresses 1 to 32, Modbus register addresses 2201 to 2232
Here, the representation in the hexadecimal form is easier to read because the data are transmitted
in the following form:
0xFFFF =
0x
F
F
F
F
0b
1111
1111
1111
1111
Local latching
DGC-06 latching
Local alarms
DGC-06 Alarms
There are 4 status bits for the 4 alarm stages each.
1 = alarm or latching active
0 = alarm or latching not active
The above example:
There are 2 local alarms at DP1, with the 2. being in latching mode.
The 1. alarm generated by the DGC-06 is present at DP4.
The 1. alarm generated by the DGC-06 is present at AP5.