9.2.2 Maintenance schedule
(*) For this purpose use specific test meters.
The above maintenance schedule is based on average operating conditions.
In some installations it may be necessary to increase the frequency of maintenance.
OPERATION
1 day
1 month
6 months
annually
Check control panel display for any alarm signals.
¡
Check that the water output temperature is within the envisaged range.
¡
Check that water inlet temperature is in compliance with the value utilised for selection of the unit.
(*)
¡
Check that the ambient temperature is lower than the value used for selecting the unit. Check that the
environment is well ventilated.
¡
Clean the water filter.
The water filter should be cleaned one week after the first start-up of the unit.
¡
Check the water level with the aid of the gauge provided.
¡
Check that the unit current absorption is with the value on the data plate. (*)
¡
Carry out visual inspection of refrigerant circuit, looking out for any deterioration of the piping or
any traces of oil which might indicate a refrigerant leak.
¡
Check the condition and security of piping connections.
¡
Check the condition and security of wiring and electrical connections.
¡
Check that fan operation is not noisy.
Clean the filter on the condenser.
Inspect the condenser fins and clean them if necessary with a soft sponge or a jet of clean
compressed air.
Check that the grilles of the unit are free from dirt and any other obstructions.
¡