EasyManua.ls Logo

MTL MTL5014 - MTL5015 Solid-State Two-Channel Switch;Proximity Detector with Line Fault Detection and Phase Reversal

Default Icon
46 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
14
INM5000-6 Jul 2010
6.4.2 Outputs
The output 1 relay reflects the status of the input and may be configured
to operate in reverse phase (PR) or with line-fault detection (LF). The
output 2 relay may be configured either to follow (slave mode) output 1
or as a line-integrity monitor (LFD) (see 6.4.3).
6.4.3 Line fault detection
(See section 3.1.4 for definition of a line fault)
Line-fault detection and the operational mode of output 2 (ie slave to
output 1 or LFD) are selected by switches located on the top of the
module (see figure 6.8).
When LFD is selected for output 2 and there is a line fault in the sensor
circuit the output 2 relay is de-energised (providing an alarm output).
When LF is selected for output 1, the output 1 relay is de-energised if
there is a line fault in the sensor circuit. Note that resistors must be fitted
when using LFD with a contact input; 500Ω to 1kΩ in series, and 20kΩ
to 25kΩ in parallel with the switch.
6.4.4 Testing
Make the relevant safe- and hazardous-area connections shown in figure
6.9 for the tests listed in table 6.3. (Figure 6.8 shows the switch positions
for configuring output 2 slave/LFD, output 1 line fault (LF) and phase
reversal (PR)).
Table 6.3
6.5 MTL5015 solid-state two-channel
switch/proximity detector with line
fault detection and phase reversal
The MTL5015 enables each of two safe-area loads to be controlled,
through a solid-state output, by a switch or proximity detector in a
hazardous area. Line fault detection (LFD) and output phase reversal
(see 3.1.3) facilities are included.
6.5.1 Wiring connections
See figure 6.10 for wiring connections.
Phase Line fault Output 1 Output 2 Status Fault
reverse detection Slave Input test switch position relay relay LED LED
Test switch (PR) (LF) (LFD) (terminals 1 & 2) (11-12) (9-8) (yellow) (red)
1 Normal Off LFD (a) i.e. short-circuit Closed Open On On
2 Reverse Off LFD (a) short-circuit (I
sc
=7–9mA) Open Open Off On
3 Normal On Slave (a) short-circuit Open Open Off On
4 Normal Off Slave (a) short-circuit Closed Closed On Off
5 Normal Off Slave open-circuit (V
oc
=7V5–9V5) Open Open Off Off
6 Normal On Slave open-circuit Open Open Off On
7 Normal Off LFD (b) 22kΩ Open Closed Off Off
8 Normal Off LFD (c) 680Ω Closed Closed On Off
LF
PR
O/P1
ON
SLAVE LFD
Output 2
MTL5014
PWR
Output 1 follows sensor
Output 2 slaves output 1
Output 1 follows sensor
Output 2 monitors LFD
Output 1 follows sensor & LFD
Output 2 slaves output 1
Output 1 follows sensor & LFD
Output 2 monitors LFD
Output 1 in phase with sensor
Output 1 in anti-phase with sensor
(LFD not affected)
6
5
4
3
2
1
7
8
9
10
11
12
13
14
Vs
Vs+
20 to 35V dc
Output 2
relay
Output 1
relay
To earth
leakage
detector
SW
22kW
680W
a
b
c
+
open
Terminal Function
1 Input –ve (Ch 1)
2 Input +ve (Ch 1)
3 Earth leakage detection
4 Input –ve (Ch 2)
5 Input +ve (Ch 2)
6 Earth leakage detection
8 Output –ve (Ch 2)
9 Output +ve (Ch 2)
11 Output –ve (Ch 1)
12 Output +ve (Ch 1)
13 Supply –ve
14 Supply +ve
6
5
4
3
2
1
7
8
9
10
11
12
13
14
To earth leakage
detector
SW
22kW
680W
a
b
c
open
22kW
+
Vs
Vs+
20 to 35V dc
} V
d2
1kW
1kW
+
+
} Vd1
Ch1
Ch2
+
Figure 6.8: Top label of MTL5014 with explanation of switch positions
Figure 6.9: Test circuit for MTL:5014
Figure 6.11: Test circuit for MTL5015
6
5
4
3
2
1
7
8
9
10
11
12
13
14
Vs
Vs+
20 to 35V dc
To earth
leakage
detector
22kW
680W
+
Resistors required only
for line fault detection
Ch 2
22kW
680W
+
Ch 1
+
+
Figure 6.10: MTL5015 wiring diagram and connections
Hazardous area Safe area
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Related product manuals