EasyManuals Logo

Munters ML420 User Manual

Munters ML420
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #21 background imageLoading...
Page #21 background image
DehumidierML420-MLT1400
5.3Airowcheckandadjustment
Toobtainthedesignperformance,thedryairandreactivationairowdampersmustbecorrectlyadjustedin
accordancewiththeratedairow,seesection9.3,Technicaldata.
Ifnecessary,contactMuntersforassistanceconcerninginstallationandsettings.Munterscontactaddresses
areprovidedonthebackcoverofthismanual.
CA CA
CA
UTION! UTION!
UTION!
Incorrectlysetprocessandreactivationairowscancausetheunittomalfunction.
Anydamagetotheunitresultingfromincorrectadjustmentoftheairowscaninvalidatethewarrantyoftheunit.
Theunitmustnotberunformorethanafewminutesbeforesettingupthecorrectairows.
1.Adjustthedampersinstalledinthedryairoutletandreactivationairinletductstothecorrectrated
airows.
2.Startthedehumidierandrunatfullpowerfor8minutestoallowthereactivationheatertoreachits
normaloperatingtemperature.
3.Verifythatthetemperaturedifferencebetweenthereactivationinletairandthereactivationtemperature
is95°C(tolerancelimit±5°C).Ifthetemperaturedifferenceliesoutsideofthe5%tolerancelimit,the
reactivationairdampercanbeadjustedinsmallstepsuntilthereactivationtemperatureiswithinthe
speciedtolerances.Allowthetemperaturetostabiliseaftereachadjustment.
Example:
Inletairtemperature=15°C
Reactivationairtemperature=110°C
Temperatureincrease=95°C
190TGB-1035-H1604Commissioning17

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Munters ML420 and is the answer not in the manual?

Munters ML420 Specifications

General IconGeneral
BrandMunters
ModelML420
CategoryDehumidifier
LanguageEnglish

Related product manuals