7.5.5. Key lock function
The key operation can be voided in order to prevent rewriting of the value set by mistake.
Once the key is locked, switching to other modes becomes unavailable except for peak
hold function. The key can not be unlocked even when the power is turned off and on
again, and can be released only by unlocking it.
In Measurement Mode, press + keys to display for about 1 second, and
the key will be locked.
Press + keys to unlock. Display for about 1 second and the key will be
unlocked.
7.5.6 Error
When the following error occurs in Measurement Mode, display error message or pressure
alternately, or follow the message to take an action.
7.5.7 Backup of settings
The built-in EEPROM holds the set value and some operating state against power failure.
圧力レンジの110%F.S.を超える圧力が印加
された時、又は表示値が6000を超えた時
圧力レンジの-10%F.S.未満の圧力が印加さ
れた時、又は表示値が-1999を超えた時
ゼロ点調整時、圧力レンジの±10%F.S.範囲
外の圧力が印加されている時
Adjust the value within the rated pressure.
Set the value to the atmospheric pressure
level and conduct zero adjustment again.
Applied pressure is lower than -10 %F.S. of pressure
range or the display value exceeds
-1999.
Applied pressure is greater than 110 %F.S. of
pressure range or the display value exceeds 6000.
Applied pressure is outside +/-10 %F.S. of pressure
range during zero adjustment.