NAPCO Gemini C-Series Control Panel Installation Instructions--Volume 2
Installation Instructions, Volume 2 Page 37
Menu" options to function (see "Function Menu" further in this manual).
Burg User Code: For Fire and Burglary combination systems, this code will only allow access to the Burglary functions of the
system. This code is typically used by a person with the responsibility of securing the premises, arming and disarming the
Burglary alarm system, silencing Burglary alarms if they occur, etc. This code is special in that each code can be assigned
four different "Authority Levels" (0. 1, 2 or 3) and five "Attributes" (Initially Off, BV, User Program, BE and Overview) and
can be assigned to Area(s) 2 - 8 (with Area 1 being reserved for Fire only).
The Gemini C-Series control panels are pre-programmed at the factory as follows:
• For Burglary-Only systems: The panel default Burg User Code is programmed as User #1, with digits 123, active in
Area 2 only.
• For Fire and Burglary combination systems: The panel default Fire User Code is programmed as User #1, with digits
"123", active in Area 1 only. The Burg User Code is programmed as User #2, with digits "456", active in Area 2 only.
• For Commercial Fire-Only systems: The panel default Fire User Code is programmed as User #1, with digits 123 active
in Area 1 only.
User Keypad Unlock
Program this feature (in the Quickloader System Assignment screen, System Reporting and Outputs tab) to allow the re-
porting to the central station when any Fire User Code is used to unlock a Fire keypad.
Waterflow
Waterflow Retard Time
A Waterflow Zone monitors sprinkler system waterflow; it is activated by an initiating device approved for that purpose. A
zone programmed as a Waterflow Zone must also be programmed as a "Zone Area 1 (Fire)" as well. For Waterflow alarms,
total maximum allowable time delay (device and panel) is 90 seconds (less any inherent delay of the waterflow sensor) for UL
installations.
Wireless Trouble Reporting by Zone
All reports of Wireless trouble (Transmitter Low Battery, Transmitter Tamper, Transmitter Supervision Failure) to central sta-
tion will identify identifying the zone of the transmitter.
Wireless/SLC Troubles to Telco 1
Wireless/SLC Troubles to Telco 3
When selected, any of the following troubles will trigger a report to the selected central station Telco number (Telco 1 or Telco
3): E04, E92 and E97.
Wireless Smoke Low Battery Resound
If a low battery is detected on a wireless smoke detector (GEMC-WL-SMK), heat detector (GEMC-WL-HEAT) or the GEMC-
WL-WD2 transmitter (if used for Fire applications), the device will re-sound the trouble at the keypad every 4 hours when dis-
armed and every 12 hours when armed, until the condition is corrected. Program this feature in the System Assignment
screen, System Options tab.
Zone Area 1–Zone Area 8
All Fire zones must be programmed for "Zone Area 1 (Fire)". See Areas
Zone Type See Data Format in the Burglary Glossary
FIRE GLOSSARY