NAPCO Gemini C-Series Control Panel Programming Instructions--Volume 2
Page 96 Programming Instructions, Volume 2
FIRE REPORTING EVENTS (ADDRESS 8020-8039)
ADDR
EVENT DESCRIPTION
FIRE
REPORTING EVENTS
OMT (One
Man Test)
User Keypad
Unlocked
User Keypad
Locked
"ENABLE
PROGRAMMING"
Mode
RF Receiver
Jam
RF Receiver
Tamper
Burg SLC
Receiver
Loop Trouble
Burg SLC
Receiver
Tamper
1 2 3 4 5 6 7 8
EVENT REPORT TELCO 1 8020
RESTORE REPORT TELCO 1 8021
EVENT REPORT TELCO 3 8022
RESTORE REPORT TELCO 3 8023
Default = blank (•) from address 8020-8023
ADDR
EVENT DESCRIPTION
FIRE
REPORTING EVENTS
Fire SLC
Receiver
Loop Trouble
Fire SLC
Receiver
Tamper
RF Receiver
No Response
Burg SLC
Receiver No
Response
Fire SLC
Receiver No
Response
Reserved Reserved Reserved
1 2 3 4 5 6 7 8
EVENT REPORT TELCO 1 8024
RESTORE REPORT TELCO 1 8025
EVENT REPORT TELCO 3 8026
RESTORE REPORT TELCO 3 8027
Default = blank (•) from address 8024-8027
UNATTENDED DOWNLOAD MODE (ADDRESS 8163 )
Unattended Download Mode
When enabled, allows unattended downloading from a
computer for Fire Alarm installations using PCD-Windows
Quickloader software. This feature is enabled ONLY by
(keypad) Direct Address Program Mode by an authorized
User regardless of the Remote Downloading Rules (see
WI1673 Volume 1) and CANNOT be overridden by Quick-
loader. This feature is disabled by default, and will not
trigger an "Error Check Required" (E28) trouble message
when enabled. Enable using Direct Address Program
Mode by pressing "1" at address 8163. To inform the
dealer if this option was enabled via the keypad, PCD-
Windows Quickloader (in the Keypad Assignment
screen, Keypad Features tab) contains a non-functional
"Unattended Download Mode" checkbox that is checked
when enabled and grayed-out when disabled.
Note: Unattended downloading from a computer is NOT
allowed for Fire Alarm UL installations.
8163
UNATTENDED DOWNLOAD MODE
Default
0 Disable
OFF
1 Enable

Other manuals for NAPCO GEMINI GEMC-128

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the NAPCO GEMINI GEMC-128 and is the answer not in the manual?

NAPCO GEMINI GEMC-128 Specifications

General IconGeneral
BrandNAPCO
ModelGEMINI GEMC-128
CategoryControl Panel
LanguageEnglish

Related product manuals