Chapter 3 Feature Set Description
FieldPoint FP-1000/1001 User Manual 3-6
©
National Instruments Corporation
When a new I/O module is connected in place of the one that was
removed, the FP-1000/1001 first verifies that the replacement I/O
module is compatible with the one that was removed. If the I/O module
is the same as, or is compatible with, the one removed, the
FP-1000/1001 configures the replacement I/O module with its
predecessor’s configuration and output value settings. It also applies the
effects of any commands sent by the host computer while the I/O
module was missing.
If the replacement module is incompatible with the one that was
removed, the FP-1000/1001 looks at the information stored in the
SnapShot. If the SnapShot is enabled and the replacement module is
compatible with the information in the SnapShot, the FP-1000/1001
configures the replacement module with the SnapShot configuration.
Otherwise, the FP-1000/1001 configures the replacement module to
factory default settings.
Table 3-1 shows how modules are configured after HotPnP
replacement.
While one or more replacement I/O modules in the bank are being
serviced by the HotPnP feature, the other I/O modules in the bank
Table 3-1. Module Configuration Results After HotPnP Replacement
SnapShot
Feature
Replacement Module
Replacement Module
Configuration After
HotPnP
Enabled/
Disabled
Compatible with the
removed module
Same as the configuration
of the removed module
Disabled Incompatible with the
removed module
Factory default
configuration of
replacement module
Enabled Incompatible with the
removed module but
compatible with the
SnapShot information
Same as the configuration
stored in the SnapShot
Enabled/
Disabled
Incompatible with the
removed module and
incompatible with the
stored SnapShot
information
Factory default
configuration of
replacement module