EasyManua.ls Logo

National Instruments NI 9411 - Safety Voltages

National Instruments NI 9411
22 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Safety Voltages
Connect only voltages that are within the following limits.
Channel-to-COM
or Vsup-to-COM
30 V maximum,
Measurement Category I
Isolation
Channel-to-channel None
Channel-to-earth ground
Continuous 30 Vrms, 42.4 Vpk, 60 VDC
Withstand 400 Vrms, verified by a 5 s
dielectric withstand test
Measurement Category I is for measurements performed on
circuits not directly connected to the electrical distribution system
referred to as MAINS voltage. MAINS is a hazardous live
electrical supply system that powers equipment. This category is
for measurements of voltages from specially protected secondary
circuits. Such voltage measurements include signal levels, special
equipment, limited-energy parts of equipment, circuits powered
by regulated low-voltage sources, and electronics.
NI 9411 Getting Started Guide | © National Instruments | 3