2-8 | ni.com
Chapter 2 Basic Functions
When operating in CC mode, the output current is maintained at the programmed current 
setpoint. The output voltage V is determined by the equation V = I
S
 × R
L
 and is less than voltage 
limit V
S
. The actual voltage that flows is determined by the current setpoint and the load 
resistance and will not necessarily be equal to the programmed value.
For loads that generate transient voltage spikes, V
S
 must be set so that the surge voltage does not 
reach the voltage limit.
Crossover Point
The RMX programmable power supply switches automatically between CV mode and CC mode 
according to the changes in the load. A crossover point is the point at which the mode switches.
For example, when operating in CV mode, if the load changes and the output current reaches the 
current limit, the RMX programmable power supply automatically switches to CC mode to 
protect the load. Likewise, when operating in CC mode, if the output voltage reaches the voltage 
limit, the RMX programmable power supply switches to CV mode.
CV Mode and CC Mode Operation Examples
This section uses a power supply with a rated output voltage of 100 V and a rated output current 
of 10 A as an example.
Example 1
A load resistance (R
L
) of 8 Ω is connected to the output terminals of the power supply. The 
output voltage and output current are set to 30 V and 5 A, respectively. In this case, 
R
C
 = 30 V/5 A = 6 Ω. Because 8 Ω is greater than 6 Ω (R
L
 > R
C
), the power supply operates in 
CV mode. When you want to increase the voltage in CV mode, you can increase the voltage up 
to the voltage defined by the following equation: Vs = Is × R
L
. Substituting the values, obtains 
Vs = 5 A × 8 Ω = 40 V. If you try to increase the voltage above this point, the crossover point is 
reached, and the power supply automatically switches to CC mode. To maintain operations in 
CV mode, increase the current limit.
Example 2
Next, a load resistance (R
L
) of 5 Ω is connected to the output terminals of the power supply. 
The output voltage and output current are set to 30 V and 5 A, respectively. In this case, 
R
C
 = 30 V/5 A = 6 Ω. Because 5 Ω is less than 6 Ω (R
L
 < R
C
), the power supply operates in 
CC mode. When you want to increase the current in CC mode, you can increase the current up 
to the current defined by the following equation: I
S
 = V
S
/R
L
. Substituting the values, obtains 
I
S
 = 30 V/5 Ω = 6 A. If you try to increase the current above this point, the crossover point is 
reached, and the power supply automatically switches to CV mode. To maintain operations in 
CC mode, increase the voltage limit.