Questions and Answers

  • M
    Margaret Perry MDSep 8, 2025
    What should I do if my NBE Boiler says the plug is disconnected?
    • D
      David EvansSep 9, 2025
      If your NBE Boiler indicates that the plug is disconnected, ensure the burner plug is properly fitted. If it is, check for dirt inside the plug and clean it of pellet dust. If there's no connection to the burner print, change the temperature sensor on the burner print.
  • D
    Darren CarrilloSep 12, 2025
    What does the 'Alarm motor output' mean on my NBE RTB 10?
    • C
      Christopher MaxwellSep 12, 2025
      An 'Alarm motor output' on your NBE Boiler can be caused by a fault current on the electric grid; try supplying the burner from another protection group. If that doesn't work, the relay might be defective, and you should send the controller in for repair.
  • J
    jbassSep 12, 2025
    Why is there no power to the controller of my NBE RTB 10 Boiler?
    • K
      Kenneth MorganSep 12, 2025
      If there is no power to the controller of your NBE Boiler, it may be due to a defective fuse in the controller, so replace the fuse with a new one. Another cause could be a deactivated safety thermostat, which can be reconnected by firmly pressing the red button. If the controller has experienced over-voltage, send the controller to NBE for repair.
  • K
    kruegerdanielleSep 14, 2025
    Why does my NBE Boiler burner deactivate residual current protection?
    • T
      Theresa GordonSep 15, 2025
      If the burner of your NBE Boiler deactivates residual current protection, the electric ignition might be faulty, so replace it with a new one. A current leak in a component could also be the cause; note when the RCD deactivates and replace the component. Check for exposed cables and insulate them if possible.
  • D
    David KellySep 16, 2025
    Why does my NBE RTB 10 have too many electric ignitions?
    • W
      wjacksonSep 16, 2025
      Too many electric ignitions in your NBE Boiler can be due to a fluctuating flow in the system; set the pressure controlled circulation pump to fixed pressure. Alternatively, an unstable external thermostat could be the cause, so set "External wait" up in the controller.