27
NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
Chapter 4 Operation
This section describes:
Turning the UPS on and off
Starting the UPS on batter y
Standby mode
The UPS front panel and indicators
Initiating the self-test
Turning the UPS On
After the UPS is connected to a power outlet, the UPS enters Standby
mode. To turn on the UPS, press and hold the
button until you hear
the UPS beep (approximately two seconds). After the UPS is turned on, it
conducts a self-test and enters Normal mode. The
µ
indicator
illuminates indicating that power is available from the UPS output
receptacles.
Starting the UPS on Battery
NOTE The UPS does not auto-detect the input frequency when starting
on battery; the default is the last frequency used by the UPS.
To turn on the UPS without using utility power, press and hold the
button for two seconds. The UPS supplies power to your equipment
and goes into Battery mode. When the UPS starts on battery, it does not
conduct a self-test to conserve battery power.
Turning the UPS Off
To turn off the UPS, press and hold the button for two seconds and
then unplug the UPS from the power outlet. If you do not unplug the
UPS, it remains in S tandby mode.