-7-
C-Series 1" & 1-1/4" WS1 Manual
Volume
Regeneration
Day
Capacity Time Option Override
Result
1
AUTO NORMAL oFF Reserve capacity automatically estimated.
Regeneration occurs when volume capacity falls below the reserve capacity at the next
Regen Set Time.
AUTO NORMAL Any Number Reserve capacity automatically estimated.
Regeneration occurs at the next Regen Set Time when volume capacity falls below the reserve
capacity or the specied number of days between regenerations is reached.
Any Number NORMAL oFF Reserve capacity NOT automatically estimated.
Regeneration occurs at the next Regen Set Time when volume capacity reaches 0.
oFF NORMAL Any Number Reserve capacity NOT automatically estimated.
Regeneration occurs at the next Regen Set Time when the specied number of days between
regenerations is reached.
Any Number NORMAL Any Number Reserve capacity NOT automatically estimated.
Regeneration occurs at the next Regen Set Time when volume capacity reaches 0 or the specied
number of days between regenerations is reached.
AUTO On 0 oFF Reserve capacity NOT automatically estimated.
Regeneration occurs immediately when volume capacity reaches 0. Time of regeneration will not
be allowed to be set because regeneration will always occur when volume capacity reaches 0.
Any Number On 0 oFF Reserve capacity NOT automatically estimated.
Regeneration occurs immediately when volume capacity reaches 0. Time of regeneration will not
be allowed to be set because regeneration will always occur when volume capacity reaches 0.
AUTO NORMAL on 0 oFF Reserve capacity automatically estimated.
Regeneration occurs when volume capacity falls below the reserve capacity at the next Regen Set
Time or regeneration occurs after 10 minutes of no water usage when volume capacity reaches 0.
AUTO NORMAL on 0 Any Number Reserve capacity automatically estimated.
Regeneration occurs at the next Regen Set Time when volume capacity falls below the reserve
capacity or the specied number of days between regenerations is reached or regeneration occurs
after 10 minutes of no water usage when volume capacity reaches 0.
Any Number NORMAL on 0 Any Number Reserve capacity NOT automatically estimated.
Regeneration occurs at the next Regen Set Time when the specied number of days between
regenerations is reached or regeneration occurs after 10 minutes of no water usage when volume
capacity reaches 0.
1 Reserve Capacity estimate is based on history of water usage. Reserve Capacity estimate is not available with
alternator systems or Twin Tank Valve.
Filters should only use shaded options
WS Controller - Setting Options Table