EasyManua.ls Logo

NetMan 204 - Page 41

NetMan 204
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
REGISTER
(1)
UPS NOMINAL DATA UNIT
NUMBER ADDRESS
73÷77
72÷76
78
77
Output nominal voltage (star)
V
79
78
Output nominal frequency
0.1*Hz
80
79
Output nominal power
100*VA
81÷83
80÷82
84
83
Battery nominal capacity (battery expansion included)
Ah
85
84
Battery benches
(1 or 2)
86
85
Battery type
Integer
87÷112
86÷111
REGISTER
(1)
UPS - COMMANDS UNIT
NUMBER ADDRESS
113
112
Command code
(2)
Integer
114
113
Shutdown delay time
Seconds
115
114
Restore delay time
Minutes
116
115
117
116
Command result
(3)
Integer
118
117
REGISTER
(1)
DIAGNOSTIC UNIT
NUMBER ADDRESS
119
118
Counter of processed correct messages
Integer
120
119
Counter of processed NOT correct messages
Integer
(1)
The register number n must be addressed n-1 in the data packet.
(2)
Refer to “Command codesparagraph
(3)
Command result = Command code if command is handled from the UPS
Command result = Command code + 100 if command is NOT handled from the UPS
Command result = 0 if Command code is wrong
- 41 -