Marking to the equipment continues to be visible and legible.
Markings and signs that are illegible shall be corrected.
Refrigeration pipe or components are installed in a position where
they are unlikely to be exposed to any substance which may corrode
refrigerant containing components, unless the components are
constructed of materials which are inherently resistant to being
corroded or are suitably protected against being so corroded.
General Warnings
Checks to electrical devices
Repair and maintenance to electrical components shall include initial
safety checks and component inspection procedures. If a fault exists
that could compromise safety, then no electrical supply shall be
connected to the circuit until it is satisfactorily dealt with.
If the fault cannot be corrected immediately but it is necessary to
continue operation, an adequate temporary solution shall be used.
This shall be reported to the owner of the equipment, so all parties are
advised.
Initial safety checks shall include:
- Those capacitors are discharged: this shall be done in a safe manner
to avoid possibility of sparking.
-That there no live electrical components and wiring are exposed while
charging, recovering or purging the system.
-That there is continuity of earth bonding.