EasyManua.ls Logo

Nextech DFS Series - Page 13

Nextech DFS Series
20 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DFS series User’s Manual REV 3.8 November 2016
13
Example:
For this example we'll assume that a lower threshold has been set to 2
lbf and the upper threshold has been set to 5 lbf:
If we were to apply a load force of say 1.5 lbf, then the yellow LED will
signal to us that the applied load has fallen below our test range
settings, resulting in a failure.
If we were to apply a load force of 6 lbf then the red LED will signal to
us that the applied load is greater than our test range settings, also
resulting in a failure.
If we were to apply a load of any force between our two range values,
for example 4 lbf, then the green LED will signal that the load has
successful fallen within our upper and lower limits, resulting in a PASS.
Example LOWER LEVEL = 0 lbf, UPPER LEVEL = 5 lbf.
Load
The “UPPER” LED will ON. Another LED OFF.
Upper level
The “OK” LED will ON. Another LED OFF.
Time
Figure 6a
Example LOWER LEVEL = 2 lbf, UPPER LEVEL = 0 lbf.
Load
The “OK” LED will ON. Another LED OFF.
Lower level
The “LOWER” LED will ON. Another LED OFF.
Time
Figure 6b