High-Vibration Application Connections
If your application is subject to high vibration, NI recommends
that you use ferrules to terminate stranded wire.
You must follow these guidelines to meet the shock and vibration
performance specifications stated in the device datasheet on
ni.com/manuals.
• Panel mount the system.
• Provide strain relief for the module by securing the cabling to
a supporting fixture no more than 8 cm (3 in.) away from the
opening of the connector backshell.
• Ensure that the supporting fixture for strain relief is stiff and
rigidly coupled to the chassis mounting surface.
• Ensure that you do not directionally bias the module when
applying strain relief.
I/O Protection
The NI 9350 provides overcurrent and short-circuit protection for
each DO channel.
28 | ni.com | NI 9350 Getting Started Guide