NI 9350 - Special Conditions for Hazardous Locations Use in Europe and Internationally

NI 9350
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Caution Do not remove modules unless power has
been switched off or the area is known to be
nonhazardous.
Caution Substitution of components may impair
suitability for Class I, Division 2, or Zone 2.
Caution The system must be installed in an enclosure
certified for the intended hazardous (classified)
location, having a tool secured cover/door, where a
minimum protection of at least IP54 is provided.
Special Conditions for Hazardous Locations Use in
Europe and Internationally
The NI 9350 has been evaluated as Ex nA IIC T4 Gc equipment
under DEMKO 12 ATEX 1202658X and is IECEx UL 14.0089X
certified. Each NI 9350 is marked II 3G and is suitable for use
in Zone 2 hazardous locations, in ambient temperatures of -40 °C
≤ Ta ≤ 70 °C. If you are using the NI 9350 in Gas Group IIC
hazardous locations, you must use the device in an NI chassis that
has been evaluated as Ex nC IIC T4, Ex IIC T4, Ex nA IIC T4, or
Ex nL IIC T4 equipment.