Here you can activate the climate systems you want +Adjust to affect. You can
also set how much effect +Adjust is to have on calculated supply temperature.
The higher the value, the greater the effect.
*Support for +Adjust required
NOTE
+Adjust must first be selected in menu 5.4 ”soft inputs/outputs”.
FLM COOLING (ACCESSORY REQUIRED)
FLM cooling 1.9.12
cool at room over temp.
room set point value
room set point value
Setting range: 20 – 30 °C
Default value: 21 °C
cool at room over temp.
Setting range: 3 – 10 °C
Default value: 3 °C
Menu
1.9.12
When you have activated FLM cooling in menu 5.3.1, set the desired room
temperature in this menu. You also select at the temperature at which cooling
is to start.
FLM cooling starts when the room temperature exceeds the set room set point
value + cool at room over temp..
FLM cooling stops when the room temperature falls below room set point value.
If you have several FLM systems, you can set these values for each of them.
43Chapter 3 | F1255 – at your serviceNIBE F1255