Cascade connection
SMO S40
F2050 (one or more) can communicate with control module
(SMO S40), by connecting the terminal block for communic-
ation (AA23-X4:1, 2, 3) in F2050 to the terminal block for
communication in SMO S40, AA100:X9-4(A), -5(B), -6(GND).
SMO S40
AA100:X9
A
GND
B
2
3
4
1
6
7
8
5
10
11
12
9
5
6
GND
GND
A
A
B
B
3
2
1
4
AA23-X4
5
6
GND
GND
A
A
B
B
3
2
1
4
AA23-X4
F2040, F2050 F2040, F2050
F2050 F2050
SMO S40
SMO 40
F2050 (one or more) can communicate with control module
(SMO 40), by connecting the terminal block for communica-
tion (AA23-X4:1, 2, 3) in F2050 to the terminal block for
communication in SMO 40, AA5:X4-1(A), -2(B), -3(GND).
Stripped length of conductor is 6 mm.
SMO 40
AA5:X4
A
GND
B
234
15
5
6
GND
GND
A
A
B
B
3
2
1
4
AA23-X4
5
6
GND
GND
A
A
B
B
3
2
1
4
AA23-X4
F2040, F2050 F2040, F2050
F2050 F2050
SMO 40
Addressing via cascade connection
On the communication board (AA23-S3), the communication
address is selected for F2050 to the control module. The
default address for F2050 is 1. In a cascade connection, all
F2050 must have a unique address. The address is coded
in binary.
S3:3S3:2S3:1Address
OFFOFFOFF1
OFFOFFOn2
OFFOnOFF3
OFFOnOn4
OnOFFOFF5
OnOFFOn6
OnOnOFF7
OnOnOn8
NIBE F2050Chapter |30