EasyManua.ls Logo

Nibe F205P - Switch Position

Nibe F205P
8 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
F205P
Dealing with malfunctions
In the event that you have no heating and/or hot water,
the heat pump switch can be set to position ”3” until the
installation engineer arrives.
In position ”3”, the heat pump compressor is disconnect-
ed. The fan and the electric heater element are in opera-
tion.
The electric heater element lamp is normally lit in position
”3” when the electric heater element is in operation. A
fault in the circuit board can cause this indication to disap-
pear. The electric heater element will still be in operation,
however, provided that its thermostat is not defective.
Art.nr. 611830
( )
( )
( )
20 100
40 80
60
ϒC
0 120
T
G
2
1
bar
3
0 4
T
G
Art.nr. 611830
20 100
40 80
60
ϒC
0 120
T
G
2
1
bar
3
0 4
T
G
Art.nr. 611830
20 100
40 80
60
ϒC
0 120
T
G
2
1
bar
3
0 4
T
G
LEK
2
3
1
20 100
40 80
60
°C
0 120
T
G
Switch position 3
The product serial number must always be
quoted in any correspondence with NIBE.
089___________
Note!
Alarms
Several of the alarms on F205P can be reset by turning the
heat pump off and back on again.
1. Set the switch (D) to position ”0”, and wait for at least
5 seconds.
2. Set the switch (D) back to position ”1”.
3. If an alarm indication is repeated, contact your in-
staller.
Art.nr. 511077
( )
20 100
40 80
60
C
0 120
T
G
2
1
bar
3
0 4
T
G

Other manuals for Nibe F205P

Related product manuals