Technical specifications
128F2120 – 1x230V
Heating
Output data according to EN 14511, partial load
1)
3.54 / 0.69 / 5.12kW/kW/-7/35 Rated output / Supplied power / COP
EN14511
3.64 / 0.91 / 4.00kW/kW/-7/45 Rated output / Supplied power / COP
EN14511
5.21/ 1.22 / 4.27kW/kW/-2/35 Rated output / Supplied power / COP
EN14511
5.27 / 1.49 / 3.54kW/kW/-2/45 Rated output / Supplied power / COP
EN14511
MaxMaxOutd. temp: /
Supply temp.
Cooling
4.69 / 1.70 / 2.7635 / 7 °C
Output data according to EN14511 ΔT5K
5.44 / 1.73 / 3.1535 / 18 °C
Specified/supplied power/EER
Electrical data
230V~50HzRated voltage
16A
rms
Max operating current, heat pump
15A
rms
Max operating current, compressor
45WMax output, fan
16A
rms
Fuse
Refrigerant circuit
R410AType of refrigerant
ScrollType of compressor
2.62.4kgVolume
4.5MPaCut-out value pressure switch HP (BP1)
0.7MPaDifference pressostat HP
0.12MPaCut-out value pressostat LP
0.7MPaDifference pressostat LP
Brine
3,4002,400m
3
/hMax airflow
-25 / 43°CMin/Max air temp, max
reverse cycleDefrosting system
Heating medium
0.45 (4.5 bar)MPaMax system pressure heating medium
0.11/0.440.08/0.32l/sMin/Max flow
65 / 25°CMax/Min heating medium temp continuous operation
G1 1/4" external thread (Ø35 mm)Connection heating medium F2120
G1 1/4" external thread (Ø35 mm)Connection heating medium flex pipe
Dimensions and weight
1,2801,130mmWidth
612610mmDepth
1,1651,070mmHeight with stand
160150kgWeight (excl. packaging)
NIBE™ F2120Chapter 10 | Technical data42