Heating medium side
DIMENSIONING THE SYSTEM
1. Check the water flow required for SAM S42 by using the
diagrams "Output transfer to the supply air". Select one
of the diagrams (supply temperature 35°C, 45°C or
55°C).
2. Check that the climate system’s pressure drop is within
the recommended range in the diagram for “Working
range SAM S42”.
3. Check that the pump capacity from the heat pump and
SAM S42 is sufficient for the heating system, using the
diagram for "Capacity, heating medium pumps".
NOTE
For supply air flows that are not in the diagrams,
an estimate (linear interpolation) can be made.
OUTPUT TRANSFER TO THE SUPPLY AIR
The diagrams show the required water flow through the
supply air coil for an 18°C supply air temperature at various
supply air flows.
Select the diagram that best matches the system’s supply
temperature at DOT (Dimensioned Outdoor Temperature).
In the diagram, DOT and supply air flow give the water flow
required.
Supply temperature 35°C at DOT
Water flow
DOT
Supply temperature 45°C at DOT
Water flow
DOT
Supply temperature 55°C at DOT
Water flow
DOT