Activating SAM S42 can be performed via the start guide or
directly in the menu system.
The main product’s software must be the latest version.
Start guide
The start guide appears upon first start-up after heat pump
installation, but is also found in menu 7.7.
Menu system
If you do not make all settings via the start guide or need to
change any of the settings, this can be done in the menu
system.
MENU 7.2.1 - ADD/REMOVE ACCESSORIES
Here, you state which accessories are installed for the
compatible product.
To identify connected accessories automatically, select
"Search for accessories". It is also possible to select accessor-
ies manually from the list.
MENU 7.2.9 - SUPPLY AIR MODULE (SAM)
Supply air temp. at low outdoor temperature
Outdoor temperature T1
Setting range: -40 - 20 °C
Supply air temperature at T1
Setting range: 16 - 22°C
Supply air temp. at medium outdoor temperature
Outdoor temperature T2
Setting range: -40 - 20 °C
Supply air temperature at T2
Setting range: 16 - 22°C
Supply air temp. at high outdoor temperature
Outdoor temperature T3
Setting range: -40 - 20 °C
Supply air temperature at T3
Setting range: 16 - 22°C
Speed contr., heating medium pump dur. heating
Manual
Setting range: on/off
Max speed, heating medium pump
Setting range: 50 - 100 %
Here, you can set temperatures for different operating
conditions and adjust settings for the speed of the circula-
tion pump.
MENU 7.1.4.2 - FAN SPEED, SUPPLY AIR
Fan speed
Normal and Fan speed 1 – Fan speed 4
Setting range: 0 – 100%
Set the speed for the five different selectable speeds for
the fan here.
Caution
Also see the Installer Manual for the main product.
SAM S42Chapter 7 | Activating SAM S4220
Activating SAM S42