Technical specifications
SAM S42
Electrical data
230 V ~ 50 HzVRated voltage
1.5WDrive output control valve
1.5WDriving power, reversing valve
75WDrive output heating medium pump
20-175WDriving power fan
IP 21Enclosure class
Heating medium circuit
0.05 / 0.5MPa/barMin pressure
0.25 / 2.5MPa/barMax pressure
53litreVolume, heating section incl. buffer vessel
Ventilation
ePM1 55%Filter type
Sound effect level according to EN 12 102
45-50dB(A)Sound power level (L
W(A)
)
1
Sound levels
41-46dB(A)Sound pressure level in the installation room (L
P(A)
)
2
Pipe connections
22mmHeating medium ext Ø
160mmVentilation Ø
Miscellaneous
600mmWidth
625mmDepth
915mmHeight
85kgWeight
067 794Part No.
1
The value varies with the selected fan curve. For more detailed sound data, including sound to channels, visit nibe.eu.
2
The value can vary with the room’s damping capacity. These values apply at a damping of 4 dB.