lected in menu 4.1.5 after the function is activated).
Activate the function by connecting potential-free
switch functions to two inputs selected in menu 5.4
(SG Ready A and SG Ready B).
Closed or open switch means one of the following:
Blocking (A: Closed, B: Open)
“SG Ready” is active. The compressor in the heat
pump and additional heat is blocked.
Normal mode (A: Open, B: Open)
"SG Ready" is not active. No effect on the system.
Low price mode (A: Open, B: Closed)
"SG Ready" is active. The system focuses on costs
savings and can for example exploit a low tariff from
the electricity supplier or over-capacity from any own
power source (effect on the system can be adjusted
in the menu 4.1.5).
Overcapacity mode (A: Closed, B: Closed)
"SG Ready" is active. The system is permitted to run
at full capacity at over capacity (very low price) with
the electricity supplier (effect on the system is set-
table in menu 4.1.5).
(A = SG Ready A and B = SG Ready B )
+Adjust
Using +Adjust, the installation communicates with
the underfloor heating’s control centre* and adjusts
the heating curve and calculated supply temperature
according to the underfloor heating system’s recon-
nection.
Activate the climate system you want +Adjust to affect
by highlighting the function and pressing the OK but-
ton.
*Support for +Adjust required
Caution
This accessory may require a software up-
date in your VVM 500. The version can be
checked in the “Service info” menu 3.1.
Visit nibeuplink.com and click on the “Soft-
ware” tab to download the latest software
to your installation.
Caution
In systems with both underfloor heating and
radiators, NIBE ECS 40/41 should be used
for optimum operation.
External blocking of functions
An external switch function can be connected to
VVM 500 for blocking various functions. The switch
must be potential-free and a closed switch results in
blocking.
NOTE
Blocking entails a risk of freezing.
Functions that can be blocked:
hot water (hot water production). Any hot water circu-
lation (HWC) remains in operation.
heating (blocking of heating demand)
cooling (blocking cooling requirement)
internally controlled additional heat
compressor in heat pump EB101
tariff blocking (additional heat, compressor, heating,
cooling and hot water are disconnected)
Possible selections for AUX output
Caution
The relay outputs may be subjected to a max
load of 2 A at resistive load (230V AC).
TIP
The AXC accessory is required if more than
one function is to be connected to the AUX
output.
Indications
alarm
common alarm
cooling mode indication (only applies if there are
cooling accessories)
holiday
away mode for "smart home" (complement to the
functions in menu 4.1.7)
Control
circulation pump for hot water circulation
active cooling in a 4-pipe system
external heating medium pump
additional heat in charge circuit
NOTE
The relevant distribution box must be marked
with a warning about external voltage.
NIBE VVM 500Chapter 5 | Electrical connections30