4.2.3 after the function has been activated). Activate the
function by connecting potential-free switch functions
to two inputs selected in menu 7.4 - "Selectable in/out-
puts" (SG Ready A and SG Ready B).
Closed or open switch means one of the following:
Blocking (A: Closed, B: Open)
“SG Ready” is active. The compressor in the air/water
heat pump and additional heat are blocked in the same
way as current tariff blocking.
Normal mode (A: Open, B: Open)
"SG Ready" is not active. No effect on the system.
Low price mode (A: Open, B: Closed)
"SG Ready" is active. The system focuses on costs sav-
ings and can for example exploit a low tariff from the
electricity supplier or over-capacity from any own power
source (effect on the system can be adjusted in the
menu 4.2.3).
Overcapacity mode (A: Closed, B: Closed)
"SG Ready" is active. The system is permitted to run at
full capacity at over capacity (very low price) with the
electricity supplier (effect on the system is settable in
menu 4.2.3).
(A = SG Ready A and B = SG Ready B )
External blocking of functions
An external switch function can be connected to VVM S320
for blocking various functions. The switch must be potential-
free and a closed switch results in blocking.
NOTE
Blocking entails a risk of freezing.
Functions that can be blocked:
heating (blocking of heating demand)
hot water (hot water production). Any hot water circulation
(HWC) remains in operation.
compressor in heat pump EB101
internally controlled additional heat
tariff blocking (additional heat, compressor, heating,
cooling and hot water are disconnected)
Possible selections for AUX output
Caution
The relay output may be subjected to a max load
of 2 A at resistive load (230V AC).
TIP
The AXC accessory is required if more than one
function is to be connected to the AUX output.
Indications
alarm
common alarm
cooling mode indication
holiday
away mode
Control
circulation pump for hot water circulation
external heating medium pump
Connecting external circulation pump
NOTE
The relevant distribution box must be marked with
a warning about external voltage.
An external circulation pump is connected to the AUX out-
put, as illustrated below.
VVMS320 External
1
2
3
NO
C
NC
AA2-X27
L N PE
L
N
PE
NIBE VVM S320Chapter 5 | Electrical connections26