3.4. Commissioning the heat pump after Installation
WARNING: Please check all the wiring carefully before turning on the heat pump.
3.4.1 Inspection Before First Trial Run
Before performing initial functional test, confirm below items and write √ in block;
Correct unit installation
Power supply voltage is the same as unit rated voltage
Correct piping and wiring
Air inlet & outlet port of unit are unblocked
Drainage and venting are unblocked and there are no water
leaks
GFCI Breaker / Current Leakage protector are working (If
required by local regulations)
Ground wire / bonding wire are connected correctly
3.4.2 Trial Run
Step 1: Run test can begin after completing the installation;
Step 2: All wiring and piping should be connected well and carefully checked, then start circulating
the water before power is switched on;
Step 3: Empty all air within the water circulation pipes, then press the “on-off” button on the control
panel to run the unit at the temperature setting;
Step 4: Items that need to be checked during the commissioning test:
Check that unit current is normal per nameplate specifications;
Check that each button on the control panel functions normally;
Check that the screen is displaying information normally and that there are no error codes;
Check for any water leaks in the circulation system;
Check that the Condensate drain is not obstructed;
Check for any abnormal sounds or vibrations?
Check that heat pump shuts off on a water flow error as soon as the water pump is turned
off

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Nirvana DISTINCTION SIM55 and is the answer not in the manual?

Nirvana DISTINCTION SIM55 Specifications

General IconGeneral
BrandNirvana
ModelDISTINCTION SIM55
CategoryHeat Pump
LanguageEnglish

Related product manuals