NORDAC FLEX (SK 200E ... SK 235E) Brief instructions for Frequency Inverters
82 BU 0240 en-US-4920
Pos: 670 /A nleit ung en/El ek tr onik /FU und Star ter /6. M eldung en zum B etrie bsz ust and /Stör m eld ung en (A ufli st ung)/ Fehl er E0 10 [ SK 1 80E/ SK 2xx E/S K2x xE-FD S] @ 40 \mod_1575965968975_14638.docx @ 2581241 @ @ 1
E010 10.0 Bus timeout (Telegram timeout/bus off 24 V int. CANbus
Data transfer is faulty. Check P513.
Check physical bus connections
Check bus protocol program process.
Check bus master.
Check 24 V supply of internal CAN/CANopen bus.
Node guarding error (internal CANopen)
Bus off error (internal CANbus)
10.2 Bus timeout option Telegram timeout
Telegram transfer is faulty.
Check physical bus connections
Check bus protocol program process.
Check bus master.
PLC is in the "STOP" or "ERROR" state.
10.4 Init error option Initialization error in bus module
Check bus module current supply.
DIP switch setting of a connected I/O extension
module is incorrect
10.1 System error option System error bus module
Further details can be found in the respective
additional bus instructions.
I/O extension:
Incorrect measurement of the input voltage or undefined
provision of the output voltage due to error in
reference voltage generation.
Short circuit at analog output
10.3
10.5
10.6
10.7
10.9 Module missing/P120 The module entered in parameter (P120) is not available.
Check connections
Pos: 67 1 /Allg emein/ Allg emeing ültig e Mod ule/---------Sei tenum bruc h k omp akt --------- @ 13\mod_1476369695906_0.docx @ 2265496 @ @ 1