2 Assembly and installation
BU 0700 EN Subject to technical alterations 11
2.4 Chassis line filter (accessory)
In contrast to the line filter described in Chapter 2.3, the HLD 110 (up
to 110kW) has a UL acceptance for the North American market.
The interference noise suppression level of class A is achieved with
up to a maximum motor cable length of 50m, and class B with motor
cables of up to 25m.
When connecting the line filter, comply with Chapter 2.9 "Wiring
guidelines" and 8.3 "EMC". In particular, ensure that the pulse
frequency is set to the default value (P504 = 4/6kHz). The line filter
should be placed as close to the side of the inverter as possible.
The connection is by means of screw connections on the upper
(mains) and lower (inverter) ends of the filter
Inverter type
SK 700E ...
Filter type
HLD 110 - ... [V] / [A]
Length
L1
Width
B1
Depth
T
Detail: mounting
Connection
cross-section
Length L2 Width B2
...-151-340-A
...-221-340-A
… 500/8
190 45 75 180 20 4 mm
2
...-301-340-A
...-401-340-A
...-551-340-A
… 500/16
250 45 75 240 20 4 mm
2
...-751-340-A
...-112-340-A
… 500/30
270 55 95 255 30 10 mm
2
...-152-340-A
… 500/42
310 55 95 295 30 10 mm
2
...-182-340-A
… 500/55
250 85 95 235 60 16 mm
2
...-222-340-A
...-302-340-O
… 500/75
270 85 135 255 60 35 mm
2
...-372-340-O
… 500/100
270 95 150 255 65 50 mm
2
...-452-340-O
...-552-340-O
… 500/130
...-752-340-O
… 500/180
380 130 181 365 102 95 mm
2
...-902-340-O
...-113-340-O
… 500/250
450 155 220 435 125 150 mm
2
Design variant, without UL, only noise suppression level A
Bus bar
...-133-340-O
HFD 103-500/300 *
564 300 160 2 x 210 275
∅ 8.5mm
...-163-340-O
HFD 103-500/400 *
∅ 10.5mm
*) without UL/cUL All dimensions in mm