5.1.1 Betriebsanzeige
BU 0700 EN Subject to technical alterations 63
5.1 Parameter description
Abbreviations: (P) = Parameter set dependent, these parameters can be set in various ways in the four parameter sets.
FI = Frequency inverter
5.1.1 Operating displays
Parameter Setting value / Description / Note Available with option
P000 Operating displays
always visible
Only with the Option ControlBox according to selection in P001.
The operating parameter selected in P001 will be displayed here.
P001 Selection of displayed value
always visible
0 ... 17
[ 0 ]
0 = Actual frequency [Hz], is the actual output frequency being supplied by the FI.
1 = Speed [1/min], is the actual rotation speed as calculated by the FI.
2 = Set frequency [Hz]: the output frequency equivalent to the actual setpoint. This need not match the
actual output frequency.
3 = Current [A]: the actual output current measured by the FI.
4 = Torque current [A]: the torque-developing output current of the FI.
5 = Voltage [Vac], the actual alternating voltage being output by the FI.
6 = DC-Link voltage [Vdc]: the FI-internal DC voltage. Amongst other things, this depends on the level of
the mains voltage.
7 = cos ϕ: the actual calculated value of the power factor.
8 = Apparent power [kVA]: the actual apparent power calculated by the FI.
9 = Effective power [kW]: the actual effective power calculated by the FI.
10 = Torque [%]: the actual torque calculated by the FI.
11 = Field [%]: the actual field in the motor calculated by the FI.
12 = On-time: time that voltage is applied to the FI network.
13 = Run-time: time that the FI is enabled.
14 = Analog input 1 [%]: actual value present at analog input 1 of the FI.
15 = Analog input 2 [%]: actual value present at analog input 2 of the FI.
16 = Position setpoint **, desired control position.
17 = Position current value **, actual position of the drive.
*) Only with SK CU1-MLT customer unit.
**) Only with the special extension unit PosiCon.
P002 Display factor
Always visible
0.01 ... 999.99
[ 1.00 ]
The operating value in parameter P001 >Selection of operating value display< is scaled with the scaling
factor and displayed in P000. It is therefore possible to display system-specific operating values such as
bottles per hour.