18
Vertical Vent Termination
Firestop
Firestop/Support
Roof
Flashing
Storm
Collar
Hanger
Strap
Horizontal Vent Termination
Hanger
Straps
Slope the
Vent Upward
Insert Bird
Screen* in
Each End
of Tee
Support
* Not supplied with water
heater, order separately.
1' (0.3m) minimum
recommended, but not required.
* Not supplied with water
heater
, order separately.
1' (0.3m) minimum
recommended, but not required.
•
•
•
•
•
•
•
•
•
•
•
•
A tee, the PVT-HL termination may be used for the vent
termination. It is not necessary to use bird screens with
the PVT-HL termination.
Terminate at least 12" (300mm) above grade or above
snow line.
Slope the horizontal vent 1/4" upwards for every 12" (300mm)
toward the termination.
Use a condensation drain if necessary.
In the Commonwealth of Massachusetts a carbon monoxide
detector is required for all side wall horizontally vented gas
fuel equipment.
Please refer to Technical Bulletin
TB 010606 for full installation
instructions.
Terminate at least 3’ (0.9m) from the combustion air intake
of any appliance andany other building opening.
Enclose exterior vent systems below the roof line to limit
condensation and protect against mechanical failure.
When the vent penetrates a floor or ceiling and is not
running in a fire rated shaft, a firestop and support is
required.
When the vent termination is located not less than
8' (2.4m) from a vertical wall or similar obstruction,
terminate above the roof at least 2' (0.6m), but not
more than 6' (1.87m), in accordance with the National
Fuel Gas Code ANSI Z223.1/NFPA 54 or Natural Gas and
Propane Installation Code CSA B149.1.
Provide vertical support every 3' (0.9m) or as required
by the vent pipe manufacturer's instructions.
A short horizontal section is recommended to prevent
debris from falling into the water heater.
When using a horizontal section, slope the horizontal
vent 1/4” upwards for every 12” (300mm) toward the
termination to drain condensate.
Exhaust
Intake
Exhaust
Intake
90 Elbow
Inlet screen
SV Conversion Kit
Accessory
(#SV-CK-4)
90 Elbow
Inlet screen
SV Conversion Kit
Accessory
(#SV-CK-4)
3” Min.
Insert Bird
Screen* in
End of 90
Elbow
Slope the
Vent Upward
When using 4" PP pipe
4" PP Adapter
ISAAN0404
4" pipe
4" pipe
When using 4" PVC/CPVC pipe
4"x4" coupling
When using 4" PP pipe
4" PP Adapter
ISAAN0404
4" pipe
4" pipe
When using 4" PVC/CPVC pipe
4"x4" coupling
Vent Pipe Installation (When supplying combustion air from the indoors (SV, non-direct vent))
* Dip switch No.3 is turned on.
•
Disconnect power and turn ON dip switch 3 if combustion air will be supplied from the
indoors as illustrated to the right. Refer to page 11 for the location of the dip switch bank.
• SV Conversion kit #SV-CK-4 is required for the air intake
.
Failure to perform the above 2 steps could result in a re or explosion causing
property damage, personal injury or death.
Refer to the instructions provided with the conversion kit for additional details.
WARNING
When installing this water heater in an area with a large amount of lint such as a commercial Laundromat,
direct-vent ("-DV") system must be used. The "-SV" conguration (using an SV conversion kit) is prohibited.
When installing this water heater in a mobile home, all combustion must be drawn directly from the outdoors.
The "-SV" conguration (using
SV conversion kit) is prohibited.