Page 4 of 10 — DN-5262 • 10/31/05
Optional
Transmitter module
(4XTM connector).
NAC or Releasing
circuits 1 & 2.
Class A or Class B,
24 VDC @ 2.5
amps each.*
Battery (12-60 A.H.)
NAC or Releasing
Circuits 3 & 4.
Class A or B, 24
VDC @ 2.5 amps
each.*
Status/Trouble
LEDs
Resettable
24 VDC @
1.25 amps*
2 non-resettable
24 VDC circuits
rated 1.25 amps
each*
AC Power 120/240 VAC
(Field Selectable)
The MPS-400
Main Power Supply
Form-C Alarm, Trouble, Supervisory,
and Security contacts. (3 amps @ 30
VDC) (
Note:
Supervisory and Security
contacts can be converted to alarm
contacts.)
Flip-Down Door
(covers the
programming
keypad)
SLC Loop #1
(Style 4, 6, or 7)
EIA-485 Port
EIA-232
Terminal Port
EIA-485 Port
“Terminal Mode”
EPROM
80-Character (2 x 40)
Back-Lit LCD Display
The CPU-300/400
SLC Loop #2
(AFP-400 only)
(Style 4,6, or 7)
EIA-232
Printer Port
Slide-in Label
Programming
Keypad
Status LED’s
Control Switches
UZC Coder Input
Door Tamper Switch (STS-200)
*The MPS-400 is a 6 amp
power supply. Total power,
including internal modules,
cannot exceed 6 amps.