Caprice Installation and Operation Instructions - Boiler Location C 85-340
6
2.0 SPECIFICATIONS
Natural Draft Application
Draft Settings (Natural Draft) - The Caprice is designed to operate with -.03” w.c. draft
in the flue breaching. For proper operation, there must be enough natural or mechanical
draft. Due to the design of the Caprice, it may operate at a positive over fire pressure up to +.20 at -.03 draft. Due
to installation and equipment variations, recommended air settings are a guideline and will require alteration. See
Tables 2-1 and 2-2.
Table 2-1 Riello Burners with Caprice Boilers (Natural Draft)
Boiler
Model
Input
GPH (US)
Heating
Capacity
MBH
Net I=B=R
Rating Water
MBH
AFUE
Efficiency
%
Pump
PSIG
Delevan
Nozzle
Recommended Burner Settings
Burner
Air
Turbulator
C85
0.68
83
72
86.8%
120
0.60 60
o
B
F3
5.5
0.0
C95
0.75
91
79
86.5%
135
0.65 60
o
B
F3
5.5
1.0
C105
0.85
103
90
86.0%
130
0.75 60
o
B
F3
5.5
1.5
C125
1.00
120
104
85.2%
140
0.85 60
o
B
F5
5.5
1.0
C150
9
1.25
147
128
83.8%
155
1.00 60
o
B
F5
5.5
1.0
C180
9
1.50
174
151
82.5%
145
1.25 60
o
B
F5
5.5
4.0
C220
1.75
216
188
86.9%
135
1.50 60
o
B
F10
5.5
0.5
C230
1.85
226
197
86.3%
150
1.50 60
o
B
F10
5.5
1.0
C250
2.00
241
210
85.5%
130
1.75 60
o
B
F10
5.5
1.5
C275
2.25
275
239
86.9%
165
1.75 60
o
B
F10
5.5
2.0
C305
2.50
304
264
86.8%
155
2.00 60
o
B
F10
5.5
3.0
C340
2.80
339
294
86.7%
155
2.25 60
o
B
F10
5.5
4.5
General Notes:
1
Output is “Heating capacityfor models C85-250 and “Gross Output” for models C275-340.
2
Models C85-180 use Riello 40 series burners.
3
Efficiency % represents Steady State in lieu of AFUE for models C275-340.
4
Energy ratings for C85-250 have been confirmed by AHRI.
5
Models C95-105 - F3 burners have an insertion depth of 2.375”.
6
Models C125-180 - F5 burners come assembled with an insertion depth of 2.375.
7
Models C220-340 - F10 burners have an insertion depth of 2.75”.
8
F10 burner heads - If head carbons on models C220-340, reduce turbulator setting and increase air a little.
9
Models C150 and C180 no longer meet minimum efficiency regulations.
Table 2-2 Beckett Burners with Caprice Boilers (Natural Draft)
Boiler
Model
Input
GPH (US)
Heating
Capacity
MBH
Net I=B=R
Rating Water
MBH
AFUE
Efficiency
%
Pump
PSIG
Delevan
Nozzle
Recommended
Burner Settings
Burner
Head
Shutter
Band
C95
0.75
91
79
86.5%
135
0.65 70
o
B
MDL1
(LFB)
-
8
1
C105
0.85
103
90
86.0%
130
0.75 70
o
B
MDL1
-
6.5
0
C125
1.00
120
104
85.2%
140
0.85 60
o
B
MDL1
-
8
1
C150
5
1.25
147
128
83.8%
155
1.00 60
o
B
MDV1
2
8
1
C180
5
1.50
174
151
82.5%
145
1.25 60
o
B
MDV1
2
10
3
General Notes:
1
Models C95-180 use Beckett AFG50 series burners.
2
“LFB” indicates the boiler must use a Low Fire Baffle (i.e. C95).
3
Energy ratings for C85-250 have been confirmed by AHRI.
4
Models C95-180 - MDL1 (NYC601) burners and MDV1 (NYC602) have an insertion depth of 3.75.
5
Models C150 and C180 no longer meet minimum efficiency regulations.