Caprice │ Installation and Operation Instructions - Boiler Location C 85-340
2.0 SPECIFICATIONS
Natural Draft Application
Draft Settings (Natural Draft) - The Caprice is designed to operate with -.03” w.c. draft
in the flue breaching. For proper operation, there must be enough natural or mechanical
draft. Due to the design of the Caprice, it may operate at a positive over fire pressure up to +.20 at -.03 draft. Due
to installation and equipment variations, recommended air settings are a guideline and will require alteration. See
Tables 2-1 and 2-2.
Table 2-1 Riello Burners with Caprice Boilers (Natural Draft)
Recommended Burner Settings
General Notes:
1
Output is “Heating capacity” for models C85-250 and “Gross Output” for models C275-340.
2
Models C85-180 use Riello 40 series burners.
3
Efficiency % represents Steady State in lieu of AFUE for models C275-340.
4
Energy ratings for C85-250 have been confirmed by AHRI.
5
Models C95-105 - F3 burners have an insertion depth of 2.375”.
6
Models C125-180 - F5 burners come assembled with an insertion depth of 2.375”.
7
Models C220-340 - F10 burners have an insertion depth of 2.75”.
8
F10 burner heads - If head carbons on models C220-340, reduce turbulator setting and increase air a little.
9
Models C150 and C180 no longer meet minimum efficiency regulations.
Table 2-2 Beckett Burners with Caprice Boilers (Natural Draft)
General Notes:
1
Models C95-180 use Beckett AFG50 series burners.
2
“LFB” indicates the boiler must use a Low Fire Baffle (i.e. C95).
3
Energy ratings for C85-250 have been confirmed by AHRI.
4
Models C95-180 - MDL1 (NYC601) burners and MDV1 (NYC602) have an insertion depth of 3.75.
5
Models C150 and C180 no longer meet minimum efficiency regulations.