EasyManua.ls Logo

NTI FTV150 - Allowable Vent and Air-Inlet Pipe Size and Lengths; Vent;Air-Inlet Pipe Length Determination; Approved Vent and Air-Inlet Pipe Material

Default Icon
88 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
General Venting FTV I&O Manual
16
Vent/Air-inlet Pipe Material
Table 4-2 Approved Vent and Air-inlet Pipe Material
Items
1
Materials
2, 3
Venting System Standards
All Vent and Air-Inlet
materials installed on gas
fired appliances in CAN/US
must meet the specifications
provided in this Table.
Failure to comply could
result in fire, serious injury
or death.
United States
Canada
4
Vent Piping
and Fittings
PVC - DWV
ANSI/ASTM D2265
In Canada, all exhaust
vent material must be
ULC S636 approved.
PVC Schedule 40
ANSI/ASTM D1785
CPVC Schedule 40
ANSI/ASTM F441
Stainless Steel (SS)
UL-1738
Polypropylene (PP)
-
Pipe Cement
PVC
ANSI/ASTM D2564
CPVC
ANSI/ASTM F493
Primers
PVC / CPVC
ANSI/ASTM F656
Notes:
1
Refer to Table 4-5 for Allowable Vent and Air-inlet Pipe Sizes and Lengths.
2
PVC venting (exhaust and air-inlet) is not permitted within the Closet/alcove of a Closet/alcove installation.
3
The Air-inlet does not require high temperature pipe material; ABS and PVC Foam Core piping is acceptable. Check
applicable local codes for acceptable materials.
The use of cellular core PVC (ASTM F891), cellular core CPVC, or Radel®
(polyphenolsulfone) in the exhaust venting system is prohibited. Failure to follow these
instructions may result in property damage, personal injury or death.
Covering non-metallic vent pipe and fittings with thermal insulation is prohibited. Failure
to follow these instructions may result in property damage, personal injury or death.
Vent/Air-inlet Pipe Length Determination
Use Table 4-3 to determine the maximum pipe length that can be used. The table calculates 90º elbows, and 45º
elbows at 5 equivalent feet each.
Example: When using 3 in. pipe, the FTV can be installed with 150 equivalent feet of air-inlet piping and 150
equivalent feet of exhaust-vent piping. See Table 4-3 for more details.
Table 4-3 Allowable Vent and Air-inlet Pipe Size and Lengths
Models
Pipe Size
(in.)
Length (ft.)
2
Number of Elbows (90’s or 45’s) and Equivalent Feet
1
2
3
4
5
6
7
8
9
FTV110/110C &
FTV150/150C Only
2
1
100
95
90
85
80
75
70
65
60
55
All FTV Models
3
150
145
140
135
130
125
120
115
110
105
Notes:
1
See WARNING below.
2
Minimum length of each the exhaust vent and combustion air-inlet piping is 6 feet equivalent.
PVC Exhaust Venting When using 2 inch PVC venting, the first seven (7) equivalent
feet of exhaust venting must be approved 2 inch CPVC or 3 inch PVC.

Table of Contents

Related product manuals