EasyManua.ls Logo

NTI Trinity Tft285 - Page 51

NTI Trinity Tft285
96 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Tft Series Installation and Operation Instructions Trinity
51
Lead Lag Instructions - Common
Plumbing install as many as 8 Tft boilers in parallel in a primary/secondary plumbing configuration as
illustrated in Figure 11-1. Size common piping as per Table 11-1.
Boiler Pump each boiler must have its own circulator (see Figure 11-1) which is controlled by its PUMP B
output; see Field Wiring Figure 12-1 and Table 12-1. The Boiler Pump must be sized according to Table 10-4.
Communication Wiring using 3-wire cable, daisy-chain terminals DATA +, DATA and DATA COM of each
boiler in parallel; see Field Wiring Table 12-2a and Figure 12-2.
System Sensor (Optional) install a system sensor (NTI P/N: 84010) on the outlet (supply) pipe feeding the
heating system, see Figure 11-1. Wire the system sensor to SENSOR COM and SYSTEM of the Master Boiler;
see Field Wiring Table 12-2a and Figure 12-2. The system sensor automatically becomes the modulation
sensor for the boiler system, i.e. the control attempts to achieve setpoint temperature at the location of the
sensor. If a system sensor is NOT used, at the Master boiler set the applicable sensor input to Unconfigured
as follows:
Configure Sensor Configuration S10 (J10-7) sensor
Outdoor Sensor (Optional) wire the outdoor sensor to SENSOR COM and OUTDOOR of any one of the
boilers in the cascade; see Field Wiring Table 12-2a and Figure 12-2. Note: only one outdoor sensor is
needed for the multiple boiler system.
Modbus Address assign a unique MB2 Modbus Address to each boiler in the cascade. Access the MB2
Modbus Address setting via the System Identification & Access menu as follows:
Configure System Identification & Access MB2 Modbus Address
Master Enable choose one (and only one) boiler in the cascade to be the Master, this boiler will receive all
control wiring and will be used for setting control parameters (see steps below). On this one boiler, set
Master enable equal to Enabled via the Lead Lag Master Configuration menu, accessed as follows:
Configure Lead Lag Master Configuration Master enable
Table 11-1 Minimum Pipe Sizes for Multiple Boiler Applications
# of
Units
Tft60
Tft85
Tft110
Tft154
Tft175
Tft201
Tft285
Tft340
Tft399
Pipe Size
2
1”
1-1/4”
1-1/2”
1-1/2”
2”
2”
2”
2-1/2”
2-1/2”
3
1-1/4”
1-1/2”
2”
2”
2”
2-1/2”
2-1/2”
3”
3”
4
1-1/2”
2”
2”
2-1/2”
2-1/2”
2-1/2”
3”
3”
3
5
1-1/2”
2”
2-1/2”
2-1/2”
3”
3”
4”
4”
4”
6
2”
2”
2-1/2”
3”
3”
4”
4”
4”
5”
7
2”
2-1/2”
2-1/2”
3”
4”
4”
4”
5
5”
8
2”
2-1/2”
3”
3”
4”
4”
4”
5”
5”
Note: Minimum pipe size based on assumed temperature rise of 25ºF at maximum firing rate.

Other manuals for NTI Trinity Tft285

Related product manuals