Cascade Instructions Vmax I&O Manual
60
Emergency Setpoint establishes an emergency (back-up) boiler operating setpoint in the event communication
is lost between boilers, or if the system sensor is not connected. Set via Installer menu setting 2-21 of each
boiler in the cascade.
VM153 Internal Diverter Valve when acting as Manager in a cascade heating an
Indirect Water Heater, the internal diverter valve of the VM153 must be “locked” in the
Central Heating position. Simply remove any DHW demand from the boiler, apply a
Central Heat demand, watch the diverter valve move to the Central Heat position
(actuator shaft retracted), then remove the electrical cable from the actuator now the
diverter valve is “locked” in the Central Heating position.