12
15. 02. 22. Document Number 672040
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk
BPS H-CO
Installation Manual
LCD Page
Number
Object Name Description Point
Type
Instance
Number
Default
Value
Range
26 Setpoint Trend Used for Trending the Temperature Setpoint TND4
27 Effective CO2 Current Effective Room CO2 AV 28528 0-100
27 Effective Humidity Current Effective Room Humidity AV 28529 0-100
27 Effective Pressure Current Effective Room Pressure AV 28530 0-100
27 Supply Fan Speed AO Supply Fan Speed Analogue Output AV 28531 0-10
27 Fresh Air Temperature
Trend
Used for Trending the Fresh Air Temperature TND7
28 Exhaust Fan Speed AO Extract Fan Speed Analogue Output AV 28532 0-10
28 Heating Output Heating Output AV 28533 0-100
28 Frost Protection
Temperature
Minimum Temperature for Frost protection
to start
AV 28640
28 Duct Static Pressure
Setpoint
Pressure Target AV 28654 400 0-1500
28 IN15 CO2 Sensor IN15 CO2 Sensor AV 28513 0-100
28 IN15 Temperature
Sensor
IN15 Temperature Sensor AV 28514 0-100
28 IN15 Humidity Sensor IN15 Humidity Sensor AV 28515 0-100
28 IN15 Pressure Sensor IN15 Pressure Sensor AV 28516 0-100
28 IN16 CO2 Sensor IN16 CO2 Sensor AV 28517 0-100
28 IN16 Temperature
Sensor
IN16 Temperature Sensor AV 28518 0-100
28 IN16 Humidity Sensor IN16 Humidity Sensor AV 28519 0-100
28 IN16 Pressure Sensor IN16 Pressure Sensor AV 28520 0-100
28 IN16 Fan Speed Control IN16 Fan Speed Control AV 28521 0-100
28 IN16 BMS 0-10v IN16 BMS 0-10v AV 28522 0-100
29 CO2 Setpoint In-Room CO2 Setpoint AV 28625 0-200
29 Deadband Temperature Deadband for Supply
temperature control
AV 28627 0-10
29 Fan Override Timeout Time period for Fan Override AV 28636 0-7200
29 Frost Protection Fan off
Delay
Delay Timer for Fan during frost protection AV 28639 0-600
29 Extract Fan Max
Demand
Extract Fan Maximum Demand AV 28631 100 0-100
29 Extract Fan Min Demand Extract Fan Minimum Demand AV 28632 20 0-100
29 Extract Fan Setback
Speed
Set the speed for the Setback AV 28634 30 0-100
29 RM199 Temp AI RM199 Temperature Sensor Analogue Input AV 28541 0-40
29 RM199 Humidity AI RM199 Humidity Sensor Analogue Input AV 28542 0 -100
29 RM201 Temp AI RM201 Temperature Sensor Analogue Input AV 28555 0-40
29 RM201 Humidity AI RM201 Humidity Sensor Analogue Input AV 28556 0 -100
29 RM201 Fan Speed
Request
RM201 Fan Speed AV 28559 0, Auto / 1, Off / 2,
Low / 3, Medium / 4,
High
29 RM201 Occupancy RM201 Occupancy AV 28560 0, Occupied / 1,
Unoccupied / 2, Bypass
/ 3, Standby
29 RM203 Fan Speed
Request
RM203 Fan Speed AV 28573 0, Auto / 1, Off / 2,
Low / 3, Medium / 4,
High