15. 02. 22. Document Number 672040
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk
BPS H-CO
Installation Manual
LCD Page
Number
Object Name Description Point
Type
Instance
Number
Default
Value
Range
29 RM203 Occupancy RM203 Occupancy AV 28574 0, Occupied / 1,
Unoccupied / 2, Bypass
/ 3, Standby
29 RM204 CO2 AI RM204 CO2 Sensor Analogue Input AV 28578 0 - 2000
29 RM204 Sensor Setpoint RM204 Setpoint AV 28579 0-100
29 RM206 CO2 AI RM206 CO2 Sensor Analogue Input AV 28592 0 - 2000
29 RM206 Sensor Setpoint RM206 Setpoint AV 28593 0-100
30 Alarm Delay A time delay for the alarm signal AV 28621 0-120
30 Auto Run-on Scale
Factor
a multiplier for the run-on timer. AV 28622 0-10
30 BMS 0-10V Input 0-10V Network Fan speed demand, along
with OUT4 output in "ESClassic BMS" mode
AV 28623 0-10
30 Fan Speed Command 0-10V Network Fan Speed Demand AV 28637 0-100
30 Extract Fan Max Voltage Extract Fan Maximum Voltage AV 28628 10 0-10
30 Extract Fan Start Volt Extract Fan Minimum Voltage AV 28629 1 0-10
30 Extract Fan Boost Speed Extract Fan Boost Speed AV 28630 100 0-100
30 RM199 CO2 AI RM199 CO2 Sensor Analogue Input AV 28543 0 - 2000
30 RM199 Sensor Setpoint RM199 Setpoint AV 28544 0-100
30 RM200 Temp AI RM200 Temperature Sensor Analogue Input AV 28548 0-40
30 RM200 Humidity AI RM200 Humidity Sensor Analogue Input AV 28549 0 -100
30 RM201 CO2 AI RM201 CO2 Sensor Analogue Input AV 28557 0 - 2000
30 RM201 Sensor Setpoint RM201 Setpoint AV 28558 0-100
30 RM202 Temp AI RM202 Temperature Sensor Analogue Input AV 28562 0-40
30 RM202 Humidity AI RM202 Humidity Sensor Analogue Input AV 28563 0 -100
30 RM202 Fan Speed
Request
RM202 Fan Speed AV 28566 0, Auto / 1, Off / 2,
Low / 3, Medium / 4,
High
30 RM202 Occupancy RM202 Occupancy AV 28567 0, Occupied / 1,
Unoccupied / 2, Bypass
/ 3, Standby
30 RM204 Temp AI RM204 Temperature Sensor Analogue Input AV 28576 0-40
30 RM204 Humidity AI RM204 Humidity Sensor Analogue Input AV 28577 0 -100
30 RM204 Fan Speed
Request
RM204 Fan Speed AV 28580 0, Auto / 1, Off / 2,
Low / 3, Medium / 4,
High
30 RM204 Occupancy RM204 Occupancy AV 28581 0, Occupied / 1,
Unoccupied / 2, Bypass
/ 3, Standby
30 RM205 CO2 AI RM205 CO2 Sensor Analogue Input AV 28585 0 - 2000
30 RM205 Sensor Setpoint RM205 Setpoint AV 28586 0-100
30 RM206 Fan Speed
Request
RM206 Fan Speed AV 28594 0, Auto / 1, Off / 2,
Low / 3, Medium / 4,
High
30 RM206 Occupancy RM206 Occupancy AV 28595 0, Occupied / 1,
Unoccupied / 2, Bypass
/ 3, Standby
31 SA-T High Limit Supply High Temperature High Limit AV 28644 50 40-60
31 Humidity Setpoint In-room humidity Setpoint AV 28645 50 40-60
31 SA-T Low Limit Supply Low Temperature Low Limit AV 28648 8 5-15