15. 02. 22. Document Number 672040
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk
BPS H-CO
Installation Manual
LCD Page
Number
Object Name Description Point
Type
Instance
Number
Default
Value
Range
31 Max Auto Run-on Run on Time AV 28649 600 0-1200
31 RM200 CO2 AI RM200 CO2 Sensor Analogue Input AV 28550 0 - 2000
31 RM200 Sensor Setpoint RM200 Setpoint AV 28551 0-100
31 RM203 Temp AI RM203 Temperature Sensor Analogue Input AV 28569 0-40
31 RM203 Humidity AI RM203 Humidity Sensor Analogue Input AV 28570 0 -100
31 RM205 Fan Speed
Request
RM205 Fan Speed AV 28587 0, Auto / 1, Off / 2,
Low / 3, Medium / 4,
High
31 RM205 Occupancy RM205 Occupancy AV 28588 0, Occupied / 1,
Unoccupied / 2, Bypass
/ 3, Standby
32 Damper Delay Damper Delay AV 28646 0 0-120
32 NFC Fan Speed Night Free Cooling Fan Speed AV 28650 60 0-100
32 Purge Fan Speed Purge Fan Speed AV 28657 60 0-100
32 Purge Low SA-T Setpoint Purge Maximum Temperature AV 28658 5 30-21
32 Purge Min Temp Purge Minimum Temperature AV 28659 15 0-30
32 Heat Boost Setpoint Heat Boost Temperature Setpoint AV 28642 35 30-40
33 RTC Max Supply Temp Return Temp Control Maximum Supply Temp AV 28660 35 30-40
33 RTC Min Supply Temp Return Temp Control Minimum Supply Temp AV 28661 12 10-20
33 Run-on (Boost) Run-On (Boost) speed AV 28662 0 0-120
33 Run-on (Enable) Run-On (Enable) speed AV 28663 0 0-120
34 Setpoint Schedule Setpoint Schedule AV 28664 0 12-28
34 Setpoint Timeout Setpoint Timeout AV 28665 0 0-7200
34 Supply Fan Max Volt Supply Temperature Max Voltage AV 28666 10 0-10
34 Supply Fan Start Volt Supply Temperature Start Voltage AV 28667 1 0-100
35 Network Setpoint Network Temperature Setpoint AV 28669 22 12-28
35 Supply Fan Boost Speed Supply Temperature Boost Speed AV 28670 100 0-100
35 Supply Fan Max Demand Supply Temperature Max Demand AV 28671 100 0-100
35 Supply Fan Min Demand Supply Temperature Min Demand AV 28672 20 0-100
36 Trickle Deadband Trickle Temperature Deadband AV 28673 5 0-10
40 Re-circ Offset Re-circulation offset temperature AV 28678 0-100
41 Fan Start Delay (BPS
Only)
For R32 Delay AV 28676 300 0-300
42 Reverse Cycle Backup
Heating
Reverse Cycle Backup Heating MSV 28679 Off Off / On

Other manuals for NuAire EcoSmart Connect Control

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the NuAire EcoSmart Connect Control and is the answer not in the manual?

NuAire EcoSmart Connect Control Specifications

General IconGeneral
BrandNuAire
ModelEcoSmart Connect Control
CategoryController
LanguageEnglish

Related product manuals