14
15. 02. 22. Document Number 672040
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk
BPS H-CO
Installation Manual
LCD Page
Number
Object Name Description Point
Type
Instance
Number
Default
Value
Range
31 Max Auto Run-on Run on Time AV 28649 600 0-1200
31 RM200 CO2 AI RM200 CO2 Sensor Analogue Input AV 28550 0 - 2000
31 RM200 Sensor Setpoint RM200 Setpoint AV 28551 0-100
31 RM203 Temp AI RM203 Temperature Sensor Analogue Input AV 28569 0-40
31 RM203 Humidity AI RM203 Humidity Sensor Analogue Input AV 28570 0 -100
31 RM205 Fan Speed
Request
RM205 Fan Speed AV 28587 0, Auto / 1, Off / 2,
Low / 3, Medium / 4,
High
31 RM205 Occupancy RM205 Occupancy AV 28588 0, Occupied / 1,
Unoccupied / 2, Bypass
/ 3, Standby
32 Damper Delay Damper Delay AV 28646 0 0-120
32 NFC Fan Speed Night Free Cooling Fan Speed AV 28650 60 0-100
32 Purge Fan Speed Purge Fan Speed AV 28657 60 0-100
32 Purge Low SA-T Setpoint Purge Maximum Temperature AV 28658 5 30-21
32 Purge Min Temp Purge Minimum Temperature AV 28659 15 0-30
32 Heat Boost Setpoint Heat Boost Temperature Setpoint AV 28642 35 30-40
33 RTC Max Supply Temp Return Temp Control Maximum Supply Temp AV 28660 35 30-40
33 RTC Min Supply Temp Return Temp Control Minimum Supply Temp AV 28661 12 10-20
33 Run-on (Boost) Run-On (Boost) speed AV 28662 0 0-120
33 Run-on (Enable) Run-On (Enable) speed AV 28663 0 0-120
34 Setpoint Schedule Setpoint Schedule AV 28664 0 12-28
34 Setpoint Timeout Setpoint Timeout AV 28665 0 0-7200
34 Supply Fan Max Volt Supply Temperature Max Voltage AV 28666 10 0-10
34 Supply Fan Start Volt Supply Temperature Start Voltage AV 28667 1 0-100
35 Network Setpoint Network Temperature Setpoint AV 28669 22 12-28
35 Supply Fan Boost Speed Supply Temperature Boost Speed AV 28670 100 0-100
35 Supply Fan Max Demand Supply Temperature Max Demand AV 28671 100 0-100
35 Supply Fan Min Demand Supply Temperature Min Demand AV 28672 20 0-100
36 Trickle Deadband Trickle Temperature Deadband AV 28673 5 0-10
40 Re-circ Offset Re-circulation offset temperature AV 28678 0-100
41 Fan Start Delay (BPS
Only)
For R32 Delay AV 28676 300 0-300
42 Reverse Cycle Backup
Heating
Reverse Cycle Backup Heating MSV 28679 Off Off / On