Chapter2.
FAN MODULE REPLACEMENT
The RTX Blade Server fan modules can be replaced while power is applied to the system
and the system is running.
2.1.Fan Module Replacement Overview
This is a high-level overview of the steps needed to replace the fan modules.
1.
Identify fan module to be replaced by locating the illuminated amber fault light and
the number silkscreened directly above the fan module.
2.
Press the green tab to release the module, pull it out from the chassis and set aside.
Caution The fan module should be replaced within 30 seconds after removal.
3.
Identify the slot where the new fan will be installed.
4.
Insert the fan until an audible click is heard from the latch on the handle.
5.
Confirm that the fault light does not light up.
2.2.Replacing the Faulty Fan Module
The fan modules can be replaced without turning off the RTC Blade Server.
Caution The fan module should be replaced within 30 seconds after removal to
prevent overheating of system components.
1.
Identify the fan module to be replaced by the illuminated amber fault light and by
the number silkscreened directly above the fan module.