X1
A
ENGLISH
EN - 14
2.4 - SELECTION OF POSITION OF THE INSIDE UNIT
To obtain the best operating performance and prevent faults or hazardous conditions, the position of indoor
unit installation must meet the following requirements:
a. Do not expose the indoor unit to heat or steam.
b. Make sure that the space to the right and left is at least 120 mm and space above the unit is at least 150
mm.(gure1).
c. The indoor unit must be installed at a minimum height of 2 metres and maximum of 3 metres from the
oor.
d.Thewallwheretheindoorunitistobexed,mustbestable,strongandsuitabletosupporttheweight.
e. There must be no obstacles for the free circulation of air both from the inlet side and especially the outlet
side. In particular, there must be no obstacles within a distance of 2000 mm.
A shorter distance could cause turbulence such to prevent correct operation of the appliance.
f. If possible, install the unit on an outdoor wall, in a way to be able to convey condensate draining to the
outside.
g.Theindoorunitmustnotbeinapositionsuchthattheairowisaimeddirectlyatthepersonsbelow
(gure3).
Table 17
Model
Length for one indoor unit
max 25 m.
Difference in height between the indoor and outdoor units “A”
max 10 m.
h. The indoor unit must not be installed directly above household appliances (television, radio, refrigerator,
etc.)oraboveaheatsource(gure2).
i. Install the indoor unit in a way that there are no obstacles, which do not allow the signals emitted by the
remotecontroltobereceived(gure4).