 Series Controllers User’s Guide 
M5451    Omega Engineering | www.omega.com 
 
3.4 Connecting Outputs 
The PLATINUM
TM
 Series supports 7 different types of outputs with the model number numeric 
designations summarized in Table 3. The unit comes preconfigured with up to 3 outputs (up to 6 outputs 
with 1/8 DIN models). Table 3 shows the base output connector connections for the different 
configurations offered. The base output configuration is the 3 numeric digits following the first dash in 
the model number. The optional isolated output expansion board offered on 1/8 DIN models can add 1 
or 3 additional isolated outputs with the numeric codes and connection positions shown in Table 3. 
Table 4 defines the abbreviated codes used in Tables 5 and 6. Please note that the SPST and SPDT 
mechanical relays have snubbers built in but only on the normally open contact side. 
Table 3 – Output Type Designations for Base Output Connector. 
3A Mechanical single pole, single throw (SPST) mechanical relay 
1A Solid state relay (SSR) 
3A Mechanical single pole, double throw (SPDT) mechanical relay 
DC pulse for connecting to an external SSR 
Analog current or voltage 
Isolated Analog current or voltage (only on output expansion board for 1/8 DIN models) 
Isolated DC pulse (“IDC” only on output expansion board for 1/8 DIN models) 
 
Table 4 – 8 Pin Output/Power Connector Wiring Summary by Configuration. 
DC pulse, DC pulse, DC pulse 
DC pulse, DC pulse, analog