2nd output group
1012H
Output value read and write of
Output 1
Unit is 0.1%, write operation is valid under manual tuning mode only.
1013H
Output value read and write of
Output 2
Unit is 0.1%, write operation is valid under manual tuning mode only.
1016H Temperature regulation value -99.9 ~ +99.9. Unit is 0.1
1017H Analog decimal setting 0 ~ 3
101CH PID parameter selection 0~5/AUTO
101DH
SV value corresponded to PID
value
Only valid within available range, unit: 0.1 scale
1020H Alarm 1 type Please refer to the contents of the “Alarm Outputs” for detail
1021H Alarm 2 type Please refer to the contents of the “Alarm Outputs” for detail
1022H Alarm 3 type Please refer to the contents of the “Alarm Outputs” for detail
1024H Upper-limit alarm 1 Please refer to the contents of the “Alarm Outputs” for detail
1025H Lower-limit alarm 1 Please refer to the contents of the “Alarm Outputs” for detail
1026H Upper-limit alarm 2 Please refer to the contents of the “Alarm Outputs” for detail
1027H Lower-limit alarm 2 Please refer to the contents of the “Alarm Outputs” for detail
1028H Upper-limit alarm 3 Please refer to the contents of the “Alarm Outputs” for detail
1029H Lower-limit alarm 3 Please refer to the contents of the “Alarm Outputs” for detail
102AH Read LED Status
b0: ALM3, b1: ALM2, b2: , b3:, b4: ALM1, b5: OUT2, b6:OUT1, b7: AT
102BH Read Pushbutton Status b1: F2, b2: Up, b3: Loop, b5: F1, b6: Down, b7: Set, 0: press down key
102CH Setting lock status
102FH Software version V1.00 indicates 0x100
1030H Start pattern number 0 ~ 15
1032H
Remaining time of the executed
step (second)
Only read
1033H
Remaining time of the executed
step (minute)
Only read
1034H No. of currently executed step Only read
1035H No. of currently executed pattern Only read
1036H
Read dynamic value in
programmable control
Only read
1039H Communication write 0: Disable (default), 1: Enable
103AH
Temperature unit display
selection
0: , 1: / ℉℃linear input (default)
103BH AT setting 0: OFF (default), 1: ON
103CH
Control RUN/STOP setting 0: STOP, 1: RUN (default), 2:END (program mode), 3: HOLD (program mode)
101FH Start step number 0 ~ 15
1200H~13FFH
Pattern 0~15 temperature set
point setting (Even number)
Pattern 0~15 execution time
setting (Odd number)
-999 ~ 9999
Time: 0 ~ 9001 minute per scale
1400H~140FH
Actual number of step setting
inside the corresponding pattern
0 ~ 15 = N, indicate that this pattern is executed from step 0 to step N
1410H~141FH
Cycle number for repeating the
execution of the correspond
pattern
0 ~ 99 indicate that this pattern has been executed for 1 ~ 100 times
1420H~142FH
Link pattern number setting of
the correspond pattern
0 ~ 15, 16 indicates the program end and keep in present step. 17 indicates the
program end and execution end. 0~15 indicates the next execution pattern
number after executing the current pattern
Address Content Definition
1100H Adjust Temperature Gain
1101H Temperature Filter Range Range of temperature filter: 10~1000, unit: 0.01 , default: 100(1.0)
1102H Temperature Filter Factor Setting range: 0~50, default: 8
1103H Reverse Output Bit1: output 2, Bit0: output 1
1104H Slope of Temperature Increase Unit: 0.1 / min or 0.1/sec (refer to CommunicationAddress 1124H)
1105H Remote Input Type Selection 0: 0~20m A , 1: 4~20m A, 2: 0~5V, 3: 1~5V, 4: 0~10V