Omega CND3 Series - Installation and Wiring; Panel Cutout and Mounting

Omega CND3 Series
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
21
1106H AT Control 0: AT(Auto-tune), 1: ST(Self-tune)
1107H Remote Input Reverse Setting 0: forward, 1: reverse
1108H Alarm 1 Function Selection Bit3: Peak Record, Bit2: Hold Enable, Bit1: Output Reverse, Bit0: Standby Enable
1109H Alarm 2 Function Selection Bit3: Peak Record, Bit2: Hold Enable, Bit1: Output Reverse, Bit0: Standby Enable
110AH Alarm 3 Function Selection Bit3: Peak Record, Bit2: Hold Enable, Bit1: Output Reverse, Bit0: Standby Enable
110BH Alarm 1 Output Delay Time Unit: second. Setting range: 0~100sec
110CH Alarm 2 Output Delay Time Unit: second. Setting range: 0~100sec
110DH Alarm 3 Output Delay Time Unit: second. Setting range: 0~100sec
110EH Upper Limit of Control Output 1 Range: lower limit of control output ~100%, unit is 0.1%
110FH Lower Limit of Control Output 1 Range: 0~upper limit of control output, unit is 0.1%
1110H Upper Limit of Control Output 2 Range: lower limit of control output~100%, unit is 0.1%
1111H Lower Limit of Control Output 2 Range: 0~upper limit of control output, unit is 0.1%
1112H
Programmable Waiting
Temeprature
Setting range: 0~1000(100.0 )
1113H Programmable Waiting Time Unit: min. Setting range: 0~900
1114H Programmable Slope Increase
Unit: 0.1/min or 0.1/sec--- (refer to Communication Address 1124H) Setting
range: 0~1000
1115H Testing Mode
1116H
Adjust Upper Limit of Analog
Linear Output 1
Adjust current: 1scale=1μA, Adjust voltage: 1scale=1mV
1117H
Adjust Lower Limit of Analog
Linear Output 1
Adjust current: 1scale=1μA, Adjust voltage: 1scale=1mV
1118H
Adjust Upper Limit of Analog
Linear Output 2
Adjust current: 1scale=1μA, Adjust voltage: 1scale=1mV
1119H
Adjust Lower Limit of Analog
Linear Output 2
Adjust current: 1scale=1μA, Adjust voltage: 1scale=1mV
111AH
Adjust Retransmission Upper
Limit
Adjust current: 1scale=1μA
111BH
Adjust Retransmission Lower
Limit
Adjust current: 1scale=1μA
111CH Event 1 Selection
0: OFF, 1: Run/Stop, 2: Change SV value, 3: PID/Manual control, 4: Switch to
Programmable Hold mode
111DH Event 2 Selection
0: OFF, 1: Run/Stop, 2: Change SV value, 3: PID/Manual control, 4: Switch to
Programmable Hold mode
111EH Event 3 Selection
0: OFF, 1: Run/Stop, 2: Change SV value, 3: PID/Manual control, 4: Switch to
Programmable Hold mode
1120H SV Control Mode Selection 0: Constant, 1: Slope increase, 2: Programmable input, 3: Remote Input
1121H Adjust Remote Compensation Setting range: -999~999
1122H Adjust Remote Gain Setting range: -999~999
1123H
Positive/Negative Selection for
Remote
0: Positive, 1: Negative
1124H Switch Slope Time Unit 0: min, 1: sec
1125H Cold Junction Compensation 0: ON, 1: OFF
1126H
Reserve the Programmable
Running Status when Power OFF
0: None, 1: Running status is saved and will continue by the previous status when
power ON.
1127H Fuzzy Gain Setting range: 1~10
1128H Fuzzy Dead Band Setting range: 0.0~PB
1129H
Save Programmable Settings
into Memory
0:None, 1: Saves the programmable settings into memory
1182H CT1 Read Value Unit: 0.1A
1183H CT2 Read Value Unit: 0.1A
1. Communication Transmission Format: Command Code: 03: read words, 06: write 1 word
ASCII Mode
Read Command Read Command Response Write Command Write Command Response
STX ’: ’ ’: ’ STX ’: ’ ’: ’ STX ’: ’ ’: ’ STX ’: ’ ’: ’
ADR 1 ‘0’ ‘0’ ADR 1 ‘0’ ‘0’ ADR 1 ‘0’ ‘0’ ADR 1 ‘0’ ‘0’
ADR 0 ‘1’ ‘1’ ADR 0 ‘1’ ‘1’ ADR 0 ‘1’ ‘1’ ADR 0 ‘1’ ‘1’
CMD 1 ‘0’ ‘0’ CMD 1 ‘0’ ‘0’ CMD 1 ‘0’ ‘0’ CMD 1 ‘0’ ‘0’