Conversion number is a coefficient of conversion between input values
and real full display range (10000 counts). See Table 3.2 below for proper
conversion number.
Table 3.2 Conversion Table
RANGE CONVERSION NUMBER
100 mV 10000 / (100 x 1) = 100
1 V 10000 / (1000 x 1) = 10
10 V 10000 / (1000 x 10) = 1
0 -20 mA 10000 / (20 x 1) = 500
3.2.6 Analog Output (Re-transmission)
Analog Output is available only, if option board is factory installed. If Analog
Output Option is not installed, the instrument will skip to Reading Adjust Menu.
Figure 3.5 Flow Chart for Analog Output (Re-transmission)
ENTER ANALOG OUTPUT MENU:
Press
a
1) Press
a
, if necessary, until
CNFG
prompt appears.
Press
d
2) Display advances to
INPT
Input Menu.
Press
a
3) Press
a
, if necessary, until Display advances to
ANLG
Analog
Output Menu.
Press
d
4) Display advances to Analog Output
ENBL
Enable or
DSBL
Disable Submenu and flashes the previous selection.
23