Omega CNI16 - ALARM 1 LOW VALUE SUBMENU; ALARM 1 HI VALUE SUBMENU

Omega CNI16
53 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
28
3.2.8 Alarm 1 Menu
Figure 3.8 Flow Chart for Alarm 1 Menu
ENTER ALARM 1 MENU:
Press a 1) Press a, if necessary, until
CNFG
prompt appears.
Press d 2) Display advances to
INPT
Input Menu.
Press a 3)
Press a, if necessary, until display advances to
ALR1
Alarm 1
Menu.
Press d 4) Display advances to
LTCH
Latch.
ALARM 1 LATCH SUBMENU:
Press
d
5) Display flashes previous selection. Press
b
to
ENBL
Enable
or
DSBL
Disable.
Press
d
6) Display shows
STRD
stored message momentarily and then
advances to
AçTV
only, if it was changed, otherwise press a to
advance to
AçTV
Active Submenu.
Latch Enabled: Alarm remains "latched" until reset. To reset already latched
alarm, select Alarm Latch Enable and press Max twice (i.e. Disable and then go
back to Latch) or from a Run Mode, push
d
twice to put the monitor in Standby
Mode and then push
d
one more time to return to the Run Mode.
Latch Disabled: Alarm remains latched only as long as the alarm condition is true.
ACTIVE SUBMENU:
Press
d
7) Display flashes previous selection. Press
b
to
ABoV
Above,
or
BELo
Below.
Press
d
8) Display shows
STRD
stored message momentarily and then
advances to
DEAD
Deadband.
DEADBAND SUBMENU:
Press
d
9) Display shows
020.0
Deadband value that can be changed
by pressing
b
or
c
.
Press
d
10) Display shows
STRD
stored message momentarily and then
advances to
ALR2
Alarm 2.