Figure A-6: E/D Module Jumper Settings
A.5.2 E Module Process Input
To configure the E module Process Inputs, set the jumpers according to these instructions.
Configure Inputs 1 and 2 for one of three analog signal types:
• For 1-5 VDC Input, remove both RTD and 4-20 jumpers.
• For 4-20 mA Input, install the 4-20 jumper.
• For RTD Input, install the RTD jumper.
Configure Inputs 3 and 4 for pulse input type:
• Signal coupling is instrument dependent:
− For AC coupled, install the two AC jumpers.
− For DC coupled, install the DC jumper.
• Signal threshold is instrument dependent:
− For a 1.5v threshold, remove the HI jumper.
− For a 3.5v threshold, install the HI jumper.