OMNI 4000/7000 Installation Guide Rev H
Page A-9
Jumper Settings
Figure A-6: E/D Module Jumper Settings
A.5.2 E Module Process Input
To configure the E module Process Inputs, set the jumpers according to these instructions.
Configure Inputs 1 and 2 for one of three analog signal types:
For 1-5 VDC Input, remove both RTD and 4-20 jumpers.
For 4-20 mA Input, install the 4-20 jumper.
For RTD Input, install the RTD jumper.
Configure Inputs 3 and 4 for pulse input type:
Signal coupling is instrument dependent:
For AC coupled, install the two AC jumpers.
For DC coupled, install the DC jumper.
Signal threshold is instrument dependent:
For a 1.5v threshold, remove the HI jumper.
For a 3.5v threshold, install the HI jumper.
DC AC
AC DC AC
INPUT3
INPUT4
AC
INPUT2
RTD
4-20
INPUT1
RTD
4-20
INPUT3INPUT4
THRESHOLD
OUT=LOW
JUMPER