Table 3-5: Back Panel Wiring of the DE Module
Pinouts
Signal Name
Signal Type
Ethernet Pigtail Wire Color
1
Net #1 TX-
Ethernet TX-
Orange/White
2
Net #1 TX+
Ethernet TX+
White/Orange
3
RS485 Port 1B
RS485 B
4
RS485 Port 1A
RS485 A
5
Net #1 RX-
Ethernet RX-
Green/White
6
Net #1 RX+
Ethernet RX+
White/Green
7
Net #2 TX-
Ethernet TX-
Orange/White
8
Net #2 TX+
Ethernet TX+
White/Orange
9
RS485 Port 2B
RS485 B
10
RS485 Port 2A
RS485 A
11
Net #2 RX-
Ethernet RX-
Green/White
12
Net #2 RX+
Ethernet RX+
White/Green
3.7.4 Serial Module
The Serial module provides two ports. By factory default, both ports are configured for RS-232
mode. Project-specific requirements may call for using the RS-485 2-wire or RS-485
4-wire mode.
The maximum number of devices connected in parallel for each port are:
12 compatible serial devices, including flow computers when using the OMNI
4000/7000 RS-232 serial ports.
32 devices when using the RS-485 mode.
Jumper blocks allow for independent selection of each port to operate in RS-232 or RS-485
mode. Figure 3-21 illustrates the factory-configured jumper settings for RS-232 wire at Port 1
and Port 2.