EasyManua.ls Logo

Omron 3G3M1-A2075-ECT - Page 132

Omron 3G3M1-A2075-ECT
850 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Power sup-
ply line
Standard
applicable
motor (kW)
Inverter model
Specifica-
tions
Molded
case circuit
breaker
(MCCB)
*1
Earth leakage circuit breaker (RCD/
ELCB)
*1
Rated cur-
rent
Rated cur-
rent
Sensitivity
current
*2
Max. fault
loop impe-
dance
With
DC
re-
ac-
tor
With
out
DC
re-
ac-
tor
With
DC
re-
ac-
tor
With
out
DC
re-
ac-
tor
Three-
phase 200
V
0.1 3G3M1-A2001-
ECT
HHD 5 5 5 5 30 mA 200 Ω
0.2 HND
3G3M1-A2002-
ECT
HHD
0.4 HND
3G3M1-A2004-
ECT
HHD
0.75 HND 10 10
3G3M1-A2007-
ECT
HHD
1.1 HND 10 10
1.5 3G3M1-A2015-
ECT
HHD 15 15
2.2 HND 20 20
3G3M1-A2022-
ECT
HHD
3 HND 20 30 20 30
3.7 3G3M1-A2037-
ECT
HHD
5.5 HND 30 40 30 40
3G3M1-A2055-
ECT
HHD 50 50
7.5 HND 40 75 40 75
3G3M1-A2075-
ECT
HHD
11 HND 50 100 50 100
3G3M1-A2110-ECT HHD
15 HND 75 125 75 125
3G3M1-A2150-
ECT
HHD
18.5 HND 100 150 100 150
3G3M1-A2185-
ECT
HHD
22 HND 175 175
*1. The frame size and model of MCCB, RCD or ELCB (with overcurrent protection function) change according to the ca-
pacity of the power transformer
. For details on selection method, refer to related technical data.
*2.
The sensitivity current setting of the TT system differs according to each country. Follow the instructions of the relevant
authority.
2 Design
2-74
M1 Series EtherCAT Type User’s Manual (I670)

Table of Contents

Related product manuals